Winco DGC-500 User Manual
Page 94
Parameter
Setting Range
DGC-500 Appendix
A-3
Low Fuel Level Alarm Threshold
0 - 100%
Low Fuel Level Pre-Alarm Enable
On or Off
Low Fuel Level Pre-Alarm Level
10 - 100%
Low Oil Pressure Arming Delay
5 - 15 sec
Low Oil Pressure Pre-Alarm Enable
On or Off
Low Oil Pressure Pre-Alarm Threshold
3 - 150 psi
Low Oil Pressure Alarm Enable
On or Off
Low Oil Pressure Alarm Threshold
3 - 150 psi
Maintenance Interval Pre-Alarm Enable
On or Off
Maintenance Interval Pre-Alarm Threshold
0 - 5,000 hrs
NFPA Level
0, 1, or 2
No-Load Cool-Down Delay
1 - 60 min
Number of Crank Cycles
1- 7
Number of Flywheel Teeth
50 - 500
Oil Pressure Sender Fail Alarm
Off or On
Overspeed Alarm Delay
0 - 500 msec
Overspeed Alarm Enable
On or Off
Overspeed Alarm Threshold
105 - 140%
Pre-Alarm Buzzer Enable
Off or On
Pre-Crank Time Delay
0 - 30 sec
Pre-Start Contact after Disconnect
Off or On
Rated Engine rpm
750 - 3,600
Sender Failure Alarm Time Delay
1 - 10 sec
Speed Signal Source
MPU, Gen Freq, or MPU-Gen
Unit ID
1 - 247
Unit System
English or Metric
Weak Battery Voltage Pre-Alarm Delay
1 - 10 sec
Weak Battery Voltage Pre-Alarm Enable
On or Off
Weak Battery Voltage Pre-Alarm Threshold
4 - 8 Vdc or 8 - 16 Vdc