Parameter

Setting Range

DGC-500 Appendix

A-3

Low Fuel Level Alarm Threshold

0 - 100%

Low Fuel Level Pre-Alarm Enable

On or Off

Low Fuel Level Pre-Alarm Level

10 - 100%

Low Oil Pressure Arming Delay

5 - 15 sec

Low Oil Pressure Pre-Alarm Enable

On or Off

Low Oil Pressure Pre-Alarm Threshold

3 - 150 psi

Low Oil Pressure Alarm Enable

On or Off

Low Oil Pressure Alarm Threshold

3 - 150 psi

Maintenance Interval Pre-Alarm Enable

On or Off

Maintenance Interval Pre-Alarm Threshold

0 - 5,000 hrs

NFPA Level

0, 1, or 2

No-Load Cool-Down Delay

1 - 60 min

Number of Crank Cycles

1- 7

Number of Flywheel Teeth

50 - 500

Oil Pressure Sender Fail Alarm

Off or On

Overspeed Alarm Delay

0 - 500 msec

Overspeed Alarm Enable

On or Off

Overspeed Alarm Threshold

105 - 140%

Pre-Alarm Buzzer Enable

Off or On

Pre-Crank Time Delay

0 - 30 sec

Pre-Start Contact after Disconnect

Off or On

Rated Engine rpm

750 - 3,600

Sender Failure Alarm Time Delay

1 - 10 sec

Speed Signal Source

MPU, Gen Freq, or MPU-Gen

Unit ID

1 - 247

Unit System

English or Metric

Weak Battery Voltage Pre-Alarm Delay

1 - 10 sec

Weak Battery Voltage Pre-Alarm Enable

On or Off

Weak Battery Voltage Pre-Alarm Threshold

4 - 8 Vdc or 8 - 16 Vdc