Winco DGC-500 User Manual
Page 88
DGC-500 Installation
5-14
4.
Press the Raise/Scroll pushbutton. The screen at right is displayed. Apply
2 Aac to the current sensing inputs for phase A (P10 and P11). Press the
Lower/Scroll pushbutton.
5.
Press the Raise/Scroll pushbutton. The screen at right is displayed. Apply
2 Aac to the current sensing inputs for phase B (P12 and P14). Press the
Lower/Scroll pushbutton.
6.
Press the Raise/Scroll pushbutton. The screen at right is displayed. Apply
2 Aac to the current sensing inputs for phase V (P15 and P17). Press the
Lower/Scroll pushbutton.
7.
Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 30 ohms across the coolant temperature sender
input (P18 and P19). Press the Lower/Scroll pushbutton.
8.
Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 60 ohms across the coolant temperature sender
input (P18 and P19). Press the Lower/Scroll pushbutton.
9.
Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 100 ohms across the coolant temperature sender
input (P18 and P19). Press the Lower/Scroll pushbutton.
10. Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 150 ohms across the coolant temperature sender
input (P18 and P19). Press the Lower/Scroll pushbutton.
11. Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 200 ohms across the coolant temperature sender
input (P18 and P19). Press the Lower/Scroll pushbutton.
12. Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 300 ohms across the coolant temperature sender
input (P18 and P19). Press the Lower/Scroll pushbutton.
13. Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 400 ohms across the coolant temperature sender
input (P18 and P19). Press the Lower/Scroll pushbutton.
14. Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 600 ohms across the coolant temperature sender
input (P18 and P19). Press the Lower/Scroll pushbutton.
15. Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 800 ohms across the coolant temperature sender
input (P18 and P19). Press the Lower/Scroll pushbutton.
16. Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 25 ohms across the oil pressure sender input (P13
and P19). Press the Lower/Scroll pushbutton.
17. Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 50 ohms across the oil pressure sender input (P13
and P19). Press the Lower/Scroll pushbutton.
18. Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 75 ohms across the oil pressure sender input (P13
and P19). Press the Lower/Scroll pushbutton.
19. Press the Raise/Scroll pushbutton. The screen at right is displayed.
Connect a resistance of 100 ohms across the oil pressure sender input (P13
and P19). Press the Lower/Scroll pushbutton.