APPENDIX A • PARAMETERS AND SETTINGS
INTRODUCTION
This appendix lists all DGC-500 parameters along with the setting range/selections for each parameter.
FRONT PANEL ADJUSTABLE PARAMETERS
Table A-1 lists the DGC-500 settings that can be adjusted through the HMI.
Table A-1. HMI Adjustable Settings
Parameter
Range
Cool-Down Time Delay
0 - 60 min
Engine Maintenance Cycle Hours Pre-Alarm
Reset/Normal
LCD Contrast
25 - 75%
Low Fuel Alarm
0 - 100%
Low Fuel Pre-Alarm
10 - 100%
Metric Conversion
On/Off
Pre-Crank Time Delay
0 - 30 sec
Pre-Start Contact Status After Disconnect
On/Off
Sender Failure Alarm Time
1 - 30 sec
ALL PARAMETERS
Table A-2 lists each DGC-500 parameter in alphabetical order. The setting range or nomenclature used by
the HMI and the BESTCOMS interface is listed beside each parameter.
Table A-2 DGC-500 Settings
Parameter
Setting Range
Accumulated Engine Runtime
0 - 99,999 hrs, 59 min
Battery Charger Failure Pre-Alarm Enable
Off or On
Battery Overvoltage Pre-Alarm Enable
On or Off
Battery Overvoltage Pre-Alarm Threshold
Off, 15 Vdc, or 30 Vdc
Battery Voltage
12 Vdc or 24 Vdc
CANBus Address
0 - 253
Communication Baud Rate
1200, 2400, or 9600
Communication Parity
None, Odd, or Even
Continuous Crank Time
1 - 60 sec
Coolant Temperature Sender Fail Alarm Enable
Off or On
Coolant Temperature Sender Fail Alarm Delay
5, 10, 15, 20, 25, or 30 min