beautypg.com

Appendix a - parameters and settings, Appendix a • parameters and settings – Winco DGC-500 User Manual

Page 92

background image

DGC-500 Appendix

A-1

APPENDIX A • PARAMETERS AND SETTINGS

INTRODUCTION

This appendix lists all DGC-500 parameters along with the setting range/selections for each parameter.

FRONT PANEL ADJUSTABLE PARAMETERS

Table A-1 lists the DGC-500 settings that can be adjusted through the HMI.

Table A-1. HMI Adjustable Settings

Parameter

Range

Cool-Down Time Delay

0 - 60 min

Engine Maintenance Cycle Hours Pre-Alarm

Reset/Normal

LCD Contrast

25 - 75%

Low Fuel Alarm

0 - 100%

Low Fuel Pre-Alarm

10 - 100%

Metric Conversion

On/Off

Pre-Crank Time Delay

0 - 30 sec

Pre-Start Contact Status After Disconnect

On/Off

Sender Failure Alarm Time

1 - 30 sec

ALL PARAMETERS

Table A-2 lists each DGC-500 parameter in alphabetical order. The setting range or nomenclature used by
the HMI and the BESTCOMS interface is listed beside each parameter.

Table A-2 DGC-500 Settings

Parameter

Setting Range

Accumulated Engine Runtime

0 - 99,999 hrs, 59 min

Battery Charger Failure Pre-Alarm Enable

Off or On

Battery Overvoltage Pre-Alarm Enable

On or Off

Battery Overvoltage Pre-Alarm Threshold

Off, 15 Vdc, or 30 Vdc

Battery Voltage

12 Vdc or 24 Vdc

CANBus Address

0 - 253

Communication Baud Rate

1200, 2400, or 9600

Communication Parity

None, Odd, or Even

Continuous Crank Time

1 - 60 sec

Coolant Temperature Sender Fail Alarm Enable

Off or On

Coolant Temperature Sender Fail Alarm Delay

5, 10, 15, 20, 25, or 30 min