Specifications -3, Specifications – Winco DGC-500 User Manual
Page 10
DGC-500 General Information
1-3
SPECIFICATIONS
Current Sensing
Accuracy:
±1% of full scale or ±2 A,
whichever is greater
Burden:
1 VA
Terminals:
P10, P11 (A-phase)
P12, P14 (B-phase)
P15, P17 (C-phase)
1 Ampere Inputs
Continuous Rating:
0.02 to 1.0 A
1 Second Rating:
2 A
5 Ampere Inputs
Continuous Rating:
0.1 to 5.0 A
1 Second Rating:
10 A
Voltage Sensing
Accuracy:
±1% of full scale or ±2 V,
whichever is greater
Burden:
1 VA
Range:
12 to 576 V rms, line-to-line
1 Second Rating:
720 V rms
Terminals:
P23 (A-phase), P26 (B-phase),
P29 (C-phase), P30 (Neutral)
Frequency
Accuracy:
±0.25% of reading or ±0.2 Hz,
whichever is greater
Display Range:
4 to 70 Hz
4 to 450 Hz (P/N 9355400111,
112 only)
Contact Sensing
Emergency Stop Input
Type:
Normally-closed dry contacts
Terminals:
P35, P39
Programmable Inputs (3)
Type:
Normally-open dry contacts
Terminals:
P2, P21 (Input 1)
P3, P21 (Input 2)
P4, P21 (Input 3)
Engine System Inputs
t Stated accuracies are subject to the accuracy of
the senders used.
Fuel Level Sensing
Accuracy:
±3% of indication or ±2%
t
Range:
33 to 240
S nominal
Terminals:
P16, P19 (common)
Coolant Temperature Sensing
Accuracy:
±3% of indication (37°C to
115°C (99°F to 239°F))
±2°, whichever is greater at
25°C (77°F)
t
Range:
62.6 to 637.5
S nominal
Terminals:
P18, P19 (common)
Oil Pressure Sensing
Accuracy:
±3% of indication (0 to 690
kPa) or ±12 kPa, whichever is
greater at 25°C (77°F)
±3% of indication (0 to 100 psi)
or ±2 psi, whichever is greater
Range:
34 to 240
S nominal
Terminals:
P13, P19 (common)
Battery Voltage Sensing
Accuracy:
±3% of indication or ±0.2 V,
whichever is greater
Nominal:
12 or 24 Vdc
Range:
8 to 32 Vdc (battery dip ride-
through to 6 Vdc for 0.75 sec)
Burden:
16 W maximum
Magnetic Pickup Sensing
Voltage Range:
3 V to 35 V peak continuous
into 13 k
S (during cranking)
Frequency Range:
32 to 10,000 Hz
Terminals:
P39 (+), P40 (–)
Engine RPM Sensing
Accuracy:
±0.5% of indication or ±2 rpm,
whichever is greater at 25°C
(77°F)
Range:
750 to 3,600 rpm
Calculated Data
Voltamperes
Accuracy:
±2% of indication or ±2 kVA,
whichever is greater
Range:
0 to 9,999 kVA
Engine Run Time
Accuracy:
±0.5% of reading or ±1 hour,
whichever is greater at 25°C
(77°F)
Range:
0 to 99,999 hours
Maintenance Interval
Accuracy:
±0.5% of reading or ±1 hour,
whichever is greater at 25°C
(77°F)
Range:
0 to 5,000 hours
Output Contacts
Engine Crank, Fuel Solenoid, and Pre-Start Relays
Rating:
30 A at 28 Vdc, make, break,
and carry
t
Terminals:
K1-N.O., COM (Engine Crank)
K2-N.O., COM (Fuel Solenoid)
K3-N.O., COM (Pre-Start)
t The contact rating is reduced to 3 A for part
numbers 9 3554 00 113 and 9 3554 00 114 when
used in a hazardous location.