DGC-500 General Information

1-3

SPECIFICATIONS

Current Sensing

Accuracy:

±1% of full scale or ±2 A,
whichever is greater

Burden:

1 VA

Terminals:

P10, P11 (A-phase)
P12, P14 (B-phase)
P15, P17 (C-phase)

1 Ampere Inputs
Continuous Rating:

0.02 to 1.0 A

1 Second Rating:

2 A

5 Ampere Inputs
Continuous Rating:

0.1 to 5.0 A

1 Second Rating:

10 A

Voltage Sensing

Accuracy:

±1% of full scale or ±2 V,
whichever is greater

Burden:

1 VA

Range:

12 to 576 V rms, line-to-line

1 Second Rating:

720 V rms

Terminals:

P23 (A-phase), P26 (B-phase),
P29 (C-phase), P30 (Neutral)

Frequency

Accuracy:

±0.25% of reading or ±0.2 Hz,
whichever is greater

Display Range:

4 to 70 Hz
4 to 450 Hz (P/N 9355400111,
112 only)

Contact Sensing

Emergency Stop Input
Type:

Normally-closed dry contacts

Terminals:

P35, P39

Programmable Inputs (3)
Type:

Normally-open dry contacts

Terminals:

P2, P21 (Input 1)
P3, P21 (Input 2)
P4, P21 (Input 3)

Engine System Inputs

t Stated accuracies are subject to the accuracy of
the senders used.

Fuel Level Sensing
Accuracy:

±3% of indication or ±2%

t

Range:

33 to 240

S nominal

Terminals:

P16, P19 (common)

Coolant Temperature Sensing
Accuracy:

±3% of indication (37°C to
115°C (99°F to 239°F))

±2°, whichever is greater at
25°C (77°F)

t

Range:

62.6 to 637.5

S nominal

Terminals:

P18, P19 (common)

Oil Pressure Sensing
Accuracy:

±3% of indication (0 to 690
kPa) or ±12 kPa, whichever is
greater at 25°C (77°F)

±3% of indication (0 to 100 psi)
or ±2 psi, whichever is greater

Range:

34 to 240

S nominal

Terminals:

P13, P19 (common)

Battery Voltage Sensing
Accuracy:

±3% of indication or ±0.2 V,
whichever is greater

Nominal:

12 or 24 Vdc

Range:

8 to 32 Vdc (battery dip ride-
through to 6 Vdc for 0.75 sec)

Burden:

16 W maximum

Magnetic Pickup Sensing
Voltage Range:

3 V to 35 V peak continuous
into 13 k

S (during cranking)

Frequency Range:

32 to 10,000 Hz

Terminals:

P39 (+), P40 (–)

Engine RPM Sensing
Accuracy:

±0.5% of indication or ±2 rpm,
whichever is greater at 25°C
(77°F)

Range:

750 to 3,600 rpm

Calculated Data

Voltamperes
Accuracy:

±2% of indication or ±2 kVA,
whichever is greater

Range:

0 to 9,999 kVA

Engine Run Time
Accuracy:

±0.5% of reading or ±1 hour,
whichever is greater at 25°C
(77°F)

Range:

0 to 99,999 hours

Maintenance Interval
Accuracy:

±0.5% of reading or ±1 hour,
whichever is greater at 25°C
(77°F)

Range:

0 to 5,000 hours

Output Contacts

Engine Crank, Fuel Solenoid, and Pre-Start Relays
Rating:

30 A at 28 Vdc, make, break,
and carry

t

Terminals:

K1-N.O., COM (Engine Crank)
K2-N.O., COM (Fuel Solenoid)
K3-N.O., COM (Pre-Start)

t The contact rating is reduced to 3 A for part
numbers 9 3554 00 113 and 9 3554 00 114 when
used in a hazardous location.