Winco DGC-500 User Manual
Page 11
DGC-500 General Information
1-4
WARNING! – EXPLOSION HAZARD
(9 3554 00 113 and 9 3554 00 114 only)
Substitution of components may impair suitability
for Class
I, Division 2.
Do not disconnect equipment unless power has
been switched off or the area is known to be non-
hazardous.
Output Contacts—continued
Programmable Relays (2)
Rating:
2 A at 30 Vdc, make break, and
carry
Terminals:
P33, P34 (Output 1)
P36, P38 (Output 2)
Horn Output
Voltage:
24 Vdc or battery voltage,
whichever is less
Current:
15 mAdc maximum
Compatible Device:
Basler P/N 29760
Terminals:
P24 (+), P25 (–)
Communication Interface
Full Duplex RS-232
Connection:
Female DB-9 connector (J1)
Baud:
1200 or 2400
Data Bits:
8
Parity:
None, Odd, or Even
Stop Bit:
1
SAE J1939 Interface
Differential
Bus Voltage:
1.5 to 3 Vdc
Maximum Voltage:
–32 to 32 Vdc (with respect to
negative battery terminal)
Communication Rate: 250 kb/s
Environment
Temperature Range
Operating:
–20°C to 60°C (–4°F – 140°F)
Storage:
–40°C to 85°C (–40°F – 185°F)
Type Tests
Shock
15 G in 3 perpendicular planes
Vibration
Swept over the following ranges for 12 sweeps in
each of three mutually perpendicular planes with each
15 minute sweep consisting of the following:
5 to 29 to 5 Hz:
1.5 G peak for 5 min.
29 to 52 to 29 Hz:
0.036" DECS-A for 2.5 min.
52 to 500 to 52 Hz:
5 G peak for 7.5 min.
Salt Fog
Tested per ASTM-117B-1989
Radio Interference
Type tested using a 5 W, hand-held transceiver
operating at random frequencies centered around 144
and 440 MHz with the antenna located within 150 mm
(6") of the device in both vertical and horizontal
planes.
Dielectric Strength
2,352 Vac at 50/60 Hz for 1 second between voltage
sensing inputs and all other circuits.
500 Vac at 50/60 Hz for 1 minute between any of the
following groups.
C Current Sensing Inputs: 8 mA
C RS-232 Port: 6 mA
UL Recognition
All DGC-500 controllers are UL recognized per
Standard 508, Standard for Industrial Control
Equipment (UL File E97035).
Part Numbers 9 3554 00 113 and 9 3554 00 114
cURus recognized per Standard 1604, Electrical
Equipment for Use in Class
I and II, Division 2, and
Class
III Hazardous (Classified) Locations, Class I,
Division 2, Groups A, B, C, D, Zone 2, Temperature
Code T5.
This equipment is suitable for use in Class
I, Division
2, Groups A, B, C, D, or nonhazardous locations only.
CSA Certification
Certified per Standard CAN/CSA-C22.2,
Number 14-95, CSA File LR 23131 (excludes P/N
9 3554 00 113, 114)
NFPA Compliance
All DGC-500 controllers comply with NFPA Standard
110, Standard for Emergency and Standby Power
Systems.
Physical
Weight:
680 g (1.5 lb)