DGC-500 HMI

2-3

Figure 2-2. DGC-500 Rear Panel HMI

Table 2-2. DGC-500 Rear Panel HMI Descriptions

Call-Out

Terminals

Description

A

P22

CHASSIS GND. This terminal provides the chassis ground
connection. The DGC-500 must be hard-wired to earth ground with
no smaller than 12 AWG copper wire.

B

P20 (+), P21 (–)

BATT. DGC-500 operating power is applied to these terminals. The
DGC-500 accepts a nominal input of 12 Vdc or 24 Vdc.

C

P35 (+), P37 (–)

P2, P3, P4

Contact Sensing Terminals

ESTOP. These terminals function as the Emergency Stop input.
Power is removed from all DGC-500 output relays when this input is
open.

PROG INPUT1, PROG INPUT2, PROG INPUT3. These three inputs
can be independently programmed to function as an auto transfer
switch input, single-phase override input, low coolant level input, fuel
leak detection input, battery charger failure input, or an auxiliary
input. The inputs accept normally-open contacts connected between
terminals P2 (PROG INPUT1), P3 (PROG INPUT2), or P4 (PROG
INPUT3) and terminal P21 (BATT –).