Parameter
Setting Range
DGC-500 Appendix
A-2
Crank Disconnect Limit
10 - 100%
Cranking Style
Continuous or Cycle
Cycle Crank Time
5 - 15 sec
DTC Support
On or Off
ECU Pulse Cycle Time
1 - 60 min
ECU Response Time-out
1 - 60 sec
ECU Settling Time
5,500 - 30,000 msec
ECU Support
On or Off
Engine Maintenance Cycle Pre-Alarm Level
0 - 5,000 hrs
Engine Shutdown Time
1 - 60 sec
Engine Start/Stop Configuration
Not Configured or
Volvo Penta
Fuel Level Sender Failure Pre-Alarm Enable
On or Off
Generator Connection
3-phase L-L
3-phase L-N
1-phase A-B
Generator CT Primary Amps
1- 5,000 Aac
Generator Frequency
50 Hz or 60 Hz
Generator kW Rating
5 - 9,999 kW
Generator PT Primary Volts
1 - 999 Vac
Generator PT Secondary Volts
1- 480 Vac
Generator Rotation
ABC or ACB
Global Sender Failure Alarm Delay
1 - 30 sec
High Coolant Temperature Alarm Delay
60 sec
High Coolant Temperature Alarm Enable
On or Off
High Coolant Temperature Pre-Alarm Enable
On or Off
High Coolant Temperature Pre-Alarm Threshold
100 - 280°F
High Coolant Temperature Alarm Threshold
100 - 280°F
LCD Contrast
25 -75%
Loss of Generator Voltage Alarm Enable
On or Off
Low Battery Pre-Alarm Delay
1 - 10 sec
Low Battery Voltage Pre-Alarm Enable
On or Off
Low Battery Voltage Pre-Alarm Threshold
6 - 12 Vdc or 12 - 24 Vdc
Low Coolant Temperature Pre-Alarm Enable
On or Off
Low Coolant Temperature Pre-Alarm Threshold
50 - 100°F
Low Fuel Level Alarm Enable
On or Off