DGC-500 BESTCOMS Software

4-12

Figure 4-15. Settings Screen, Input Setup Tab

CANBus/J1939 Interface - Enable ECU Support. This setting enables and disables the DGC-500 CAN
interface. When enabled, the CAN interface allows the DGC-500 to communicate with the engine control unit
(ECU). This setting must be enabled in order to enable DTC support.

CANBus/J1939 Interface - Enable DTC Support. This setting enables and disables the viewing of diagnostic
trouble codes (DTCs) reported by the ECU. Both the Enable ECU Support and Enable DTC Support settings
must be enabled to view DTCs.

CANBus/J1939 Interface - Unit CANBus Address. This setting selects the address to be used by the DGC-500
for J1939 communication. A value of 0 to 253 may be entered.

CANBus/J1939 Interface - Engine Start/Stop Config. This setting selects one of two engine start/stop
configurations. Selecting Volvo Penta configures the DGC-500 for starting and stopping of the engine using
the J1939 communication interface. (The Enable ECU Support setting must be enabled.) Selecting Not
Configured disables this feature.

Programmable Inputs and Outputs

Click the PROG I/O button to access the Programmable Inputs and Outputs screen or click Screens on the
menu bar and click Input/Output Settings.

The Programmable Inputs and Outputs screen consists of two tabs: Input Setup and Output Setup.

Input Setup Tab

The Input Setup tab settings of the Programmable Inputs and Outputs screen consist of three identical groups
of settings for each of the three programmable inputs. Tab settings are shown in Figure 4-15. Each tab setting
is described in the following paragraphs.

Programmable Input - Function. This setting selects the function type that is used to trigger the corresponding
programmable input. The functions available for triggering a programmable input are listed below.

C

Auto Transfer Switch

C

Auxiliary Input

C

Battery Charger Fail

C

Fuel Leak Detect

C

Low Coolant Level

C

No Function

C

Single-Phase Override