Winco DGC-500 User Manual
Page 16
Call-Out
Terminals
Description
DGC-500 HMI
2-4
D
P39 (+), P40 (–)
P13
P16
P18
P19
Transducer Terminals
MPU. These terminals accept the output from a magnetic pickup.
Voltage applied to this input is scaled and conditioned for use as a
speed signal.
OIL PRESS. The output from an oil pressure transducer is applied to
this input. A current signal lower than 5 mA can be applied between
terminal P13 and P19 (SENDER COMM).
FUEL LEVEL. The output from a fuel level transducer is applied to
this input. The DGC-500 supplies a transducer current signal of less
than 30 mA to terminals P13 and P19 (SENDER COMM).
COOLANT TEMP. The output from a coolant temperature transducer
is applied to this input. The DGC-500 supplies a transducer current
signal of less than 5 mA to terminals P16/P18 and P19 (SENDER
COMM).
SENDER COMM. This terminal functions as the common return line
for all of the transducer inputs.
E
P23
P26
P29
P30
Voltage Sensing Terminals
VOLT PH A. This terminal senses the A-phase generator voltage.
VOLT PH B. This terminal senses the B-phase generator voltage.
VOLT PH C. This terminal senses the C-phase generator voltage.
VOLT NEUTRAL. This terminal connects to the generator Neutral in
phase-to-neutral sensing applications.
F
P10(
1/5A
), P11(
COM
)
P12(
1/5A
), P14(
COM
)
P15(
1/5A
), P17(
COM
)
Current Sensing Terminals
PHASE A CT. These terminals sense the A-phase generator current.
PHASE B CT. These terminals sense the B-phase generator current.
PHASE C CT. These terminals sense the C-phase generator current.
G
P24 (+), P25(–)
HORN. This output supplies power to an external horn. The voltage
supplied is 24 Vdc or the battery voltage, whichever is less. A
maximum current of 15 mAdc is available.
H
J2
SAE J1939 Connector. This connector is enabled on controllers with
a style number of FXJ and provides high-speed communication
between the DGC-500 and the ECU on an electronically controlled
engine.
I
J1
RS-232 COMMUNICATION PORT. This DB9 connector uses serial
communication to enhance DGC-500 setup. A standard serial cable
connects the DGC-500 to a PC.
J
K1-N.O., K1-COM
K2-N.O., K2-COM
K3-N.O., K3-COM
P33, P34
P36, P38
Output Contact Terminals
CRANK. This output is closed when the DGC-500 is initiating engine
cranking.
FUEL. This output closes when engine cranking is initiated and
remains closed until a stop command is received by the DGC-500.
PRE-START. This output closes to energize the glow plugs prior to
engine cranking. Depending on system setup, the Pre-Start output
may open upon engine startup or stay closed during engine
operation.
PROGRAM OUTPUT1. This output closes when a user-
programmable condition is detected by the DGC-500.
PROGRAM OUTPUT2. This output closes when a user-
programmable condition is detected by the DGC-500.