beautypg.com

Winco DGC-500 User Manual

Page 16

background image

Call-Out

Terminals

Description

DGC-500 HMI

2-4

D

P39 (+), P40 (–)

P13

P16

P18

P19

Transducer Terminals

MPU. These terminals accept the output from a magnetic pickup.
Voltage applied to this input is scaled and conditioned for use as a
speed signal.

OIL PRESS. The output from an oil pressure transducer is applied to
this input. A current signal lower than 5 mA can be applied between
terminal P13 and P19 (SENDER COMM).

FUEL LEVEL. The output from a fuel level transducer is applied to
this input. The DGC-500 supplies a transducer current signal of less
than 30 mA to terminals P13 and P19 (SENDER COMM).

COOLANT TEMP. The output from a coolant temperature transducer
is applied to this input. The DGC-500 supplies a transducer current
signal of less than 5 mA to terminals P16/P18 and P19 (SENDER
COMM).

SENDER COMM. This terminal functions as the common return line
for all of the transducer inputs.

E

P23

P26

P29

P30

Voltage Sensing Terminals

VOLT PH A. This terminal senses the A-phase generator voltage.

VOLT PH B. This terminal senses the B-phase generator voltage.

VOLT PH C. This terminal senses the C-phase generator voltage.

VOLT NEUTRAL. This terminal connects to the generator Neutral in
phase-to-neutral sensing applications.

F

P10(

1/5A

), P11(

COM

)

P12(

1/5A

), P14(

COM

)

P15(

1/5A

), P17(

COM

)

Current Sensing Terminals

PHASE A CT. These terminals sense the A-phase generator current.

PHASE B CT. These terminals sense the B-phase generator current.

PHASE C CT. These terminals sense the C-phase generator current.

G

P24 (+), P25(–)

HORN. This output supplies power to an external horn. The voltage
supplied is 24 Vdc or the battery voltage, whichever is less. A
maximum current of 15 mAdc is available.

H

J2

SAE J1939 Connector. This connector is enabled on controllers with
a style number of FXJ and provides high-speed communication
between the DGC-500 and the ECU on an electronically controlled
engine.

I

J1

RS-232 COMMUNICATION PORT. This DB9 connector uses serial
communication to enhance DGC-500 setup. A standard serial cable
connects the DGC-500 to a PC.

J

K1-N.O., K1-COM

K2-N.O., K2-COM

K3-N.O., K3-COM

P33, P34

P36, P38

Output Contact Terminals

CRANK. This output is closed when the DGC-500 is initiating engine
cranking.

FUEL. This output closes when engine cranking is initiated and
remains closed until a stop command is received by the DGC-500.

PRE-START. This output closes to energize the glow plugs prior to
engine cranking. Depending on system setup, the Pre-Start output
may open upon engine startup or stay closed during engine
operation.

PROGRAM OUTPUT1. This output closes when a user-
programmable condition is detected by the DGC-500.

PROGRAM OUTPUT2. This output closes when a user-
programmable condition is detected by the DGC-500.