beautypg.com

0 coil maintenance, 0 drive components (cont'd) – Reznor MAPSII Series REDA Users Manual User Manual

Page 8

background image

Form O-MAPS II, P/N 209179 R7, Page 8

Condenser Coil

Connections

Coils in the Cabinet (Evaporative Coils)

1. Verify that the electrical power has been turned

off and the disconnect switch locked.

2. Open the access panels.

3. Use a soft brush to remove any dirt and debris

from both sides of the coil.

4. Spray with cold or warm (not hot) water and a

cleaning solution (non-acid based coil cleaner is

recommended). Due to possible damage to the

coil, high pressure spray is not recommended.

First spray the leaving airflow side, then the inlet

airflow side.

As much as possible, spray the solution perpen-

dicular to the face of the coil.

Follow the instructions on the cleaning solution.

When cleaning process is complete, rinse both

sides with cool, clean water.

5. Replace the panels.

Coils on the Side of the Cabinet (Condenser

Coils)

The entering airflow side of the condenser coils can

be reached for cleaning without removing any com-

ponents. Remove the access panel on the end of

the condenser section to access leaving side and

additional coils.

1. Verify that the electrical power has been turned

off and the disconnect switch locked.

2. Use a soft brush to remove any dirt and debris

from the coil.

3. Spray with cold or warm (not hot) water and a

cleaning solution (non-acid based coil cleaner is

recommended). Due to possible damage to the

coil, high pressure spray is not recommended.

Spray up through the coil. Follow the instructions

on the cleaning solution. When clean, rinse with

cool, clean water.

5.0 Coil

Maintenance

Inspect all cooling coils at the beginning of the cooling season or more often if

needed.

Coil Access - The entering air side of the condenser coils is visible on the

outside of the system. For additional inspection, remove the tubing access

panel.

The evaporative coils can be accessed by opening the coil cabinet door (See

FIGURE 1).

Coil Maintenance - Inspect coils for debris, dirt, grease, lint, pollen, mold, or

any element which would obstruct heat transfer or airflow. Inspect coils and

tubing for physical damage. Inspect feeders, piping connections, coil headers,

and return bends for signs of fatigue, rubbing, and physical damage.
Clean the coils annually, or more often if needed. Use the proper tools and

follow the instructions carefully to avoid damaging the coil. Use of a non-acid

based coil cleaner is recommended. Due to possible damage to the coil, high

pressure spray is not recommended.

MODELS: 037, 025 (bottom circuit only)

FIGURE 3B - One

Twinned Circuit

FIGURE 3A - Two Single Circuits

FIGURE 3C - Three Single Circuits

Sizes

Ckt A Ckt B

059. 060

3 ton

2 ton

077, 078, 102 4.5 ton 2 ton
090, 114

4.5 ton 3 ton

108, 126

6.2 ton 3 ton

Sizes

Ckt A

025 (bottom ckt only) 2 ton
037

3 ton

Sizes

Ckt A Ckt B Ckt C

184, 220 4.5 ton 6.2 ton 4.5 ton

198, 234 4.5 ton 6.2 ton 6.2 ton

If additional cleaning is required or if coils are removed for any reason, refer to

FIGURES 3A-3L for making condenser coil connections.

The belt tension should be checked at regular maintenance inspections. Proper

belt tension is important to the long life of the belt and motor.

Be sure the belt is aligned in the pulleys. If belt is removed or replaced, be sure

to align directional arrows on the belt to the proper drive rotation.

4.0 Drive

Components

(cont'd)