beautypg.com

Reznor MAPSII Series REDA Users Manual User Manual

Page 15

background image

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 15

Step 5. Braze on Suction and Discharge Lines

Flow an inert gas, such as nitrogen (N2)

, through the system at approxi-

mately 2 psig. This will reduce the possibility of oxidation inside the tubing.

Braze on the suction and discharge lines and braze the process tube shut

following the recommendations listed below. NOTE: If the process tube

is to be used for charging the system, it should be brazed shut after

the system has been charged.

If the test for acid in

Step 2 did indicate compressor burnout, do the

following:

a) Install an acid-removing liquid line filter drier. Size he acid-removing filter

drier at least one capacity size larger than normally required for the circuit.

b) Install a temporary filter drier in the suction line. The temporary suction

line drier should be sized properly for the circuit and have a service access

fitting to monitor pressure drop across the drier.

Step 12 includes the remaining procedures required for cleanup of a com-

pressor burnout. Continue to

Step 5.

WARNING: Wearing

eye protection is

recommended.

Brazing Recommendations and Procedures

COPPER TUBING: If additional copper tubing is required, use only clean,

dehydrated refrigeration grade tubing with sealed ends.
BRAZING ALLOYS: CAUTION: Do not use 95/5, 50/50 or 40/60 soft solder

for brazing. Use Sil-Fos or Phos Copper, or similar brazing alloys with high

tensile strength on copper welds only. Weld steel to copper only with silver

brazing alloys.
BRAZING PROCEDURE: Comply with applicable code requirements and fol-

low safe brazing procedures. The manufacturer recommends the following

steps:

a) Exercise extreme care when cutting and forming tubes to keep dirt,

filings, and other contaminants out of the system.

b) Do not use excessive amounts of brazing alloy as some of the

excess may penetrate the joint and enter the system.

c) If flux must be used, take necessary precautions to ensure that the

flux does not enter the system.

d) Use damp cloths or other heat absorbent material to ensure that

the factory brazed joints on the compressor do not become dam-

aged. If

damp cloths are used, take care not to allow moisture to

enter the system.

CAUTION: Do not leave system open to the atmosphere any

longer than minimum required. This applies to all refriger-

ants but is more critical with R407C which uses POE oil. POE

oil is extremely susceptible to moisture absorption.

e) Do not overheat brazed joints as excess heat will cause formation

of copper oxide on the inside wall of the tubing. To aid in avoiding

the formation of copper oxide, flow an inert gas through the sys-

tem, as explained above.

 Step 6. Check System for Leaks

After installation is complete, pressurize the system to approximately 75

psig using nitrogen and a few ounces of refrigerant. Check for leaks using

a halide torch, soap bubbles, or an electronic halogen leak detector. When

all connections test satisfactorily, release pressure using proper recovery

procedures, then proceed to the next step.