beautypg.com

Reznor MAPSII Series REDA Users Manual User Manual

Page 19

background image

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 19

tension counterclockwise until the spring tension is relieved.

Count and

record the number of turns required so that you can return the bypass

valve to its original setting.

Instructions for Checking and Adjusting the Superheat of an Isolated

Circuit:

Step 1) Measure and record the temperature (insulate probe from sur-

rounding air temperature) and the pressure of the suction line at the com-

pressor.

Step 2) From the Temperature/Pressure Conversion Chart on the left, con-

vert the pressure measured in

Step 1 to temperature.

Step 3) Subtract measured temperature in Step 1 from the temperature

taken from the Conversion Chart in

Step 2. The answer is the degrees of

superheat.

Recommended superheat range is 8-12°F (4.5-6.7°C).

Step 4) Superheat is adjusted at the thermal expansion valve. To reduce

superheat, turn the adjusting stem

counterclockwise. To increase the

superheat, turn the adjusting stem

clockwise. Adjust and check until

superheat is within the recommended range.

Step 5) Repeat Steps 1-4 for each refrigeration circuit.

Instructions for Checking and Adjusting the Subcooling of an Iso-

lated Circuit:

Step 1) Measure and record the temperature (insulate probe from sur-

rounding air temperature) and the pressure of the liquid line at the con-

denser coil outlet.

Step 2) From the Temperature/Pressure Conversion Chart on the previous

page, convert the pressure measured in

Step 1 to temperature.

Step 3) Subtract measured temperature in Step 1 from the temperature

taken from the Conversion Chart in

Step 2. The answer is the degrees of

subcooling.

Recommended subcooling range is 18-22°F (10.1-12.3°C).

Step 4) Subcooling is adjusted by the amount of refrigerant charge. To

reduce subcooling, remove refrigerant. To increase subcooling, add refrig-

erant. Adjust refrigerant and check until subcooling is within the recom-

mended range.

 Step 12.
If the acid test in

Step 2 indicated a compressor burnout, do the following:

a) Operate the unit for several hours. Check the pressure drop through the

temporary suction line filter drier. If the pressure drop exceeds 8 psig,

recover the refrigerant, replace the suction line filter drier with the same

type as removed, replace the liquid line filter drier, evacuate the circuit, and

re-charge with the recovered refrigerant.

Continue to monitor the pressure drop through the suction line filter drier

and repeat the process above until the pressure does not exceed 8 psig

after several hours of operation.

b) Allow the system to operate for 4-8 hours. Recover the refrigerant and take

an oil sample. Retest the oil for acid.

c) If the test for acid is negative, remove the suction line filter drier, replace

the liquid line drier, evacuate, and re-charge the system with the recovered

refrigerant.

If the test indicates acid, replace both the liquid line filter drier and the suc-

tion line filter drier and repeat b) and c).

d) Verify subcooling and superheat (Refer to

Step 11.).

e) When the system is operating properly, remove the gauges.

IMPORTANT:

Do not release

refrigerant to the

atmosphere! If

required service

procedures

include the adding

or removing of

refrigerant, the

qualified HVAC

service technician

must comply with

all federal, state

or provincial, and

local laws.

Step 5) Repeat Steps 1) - 4 ) for each refrigeration circuit.