beautypg.com

Reznor MAPSII Series REDA Users Manual User Manual

Page 17

background image

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 17

��������

�������

����������

���������

����������

�������

����������

�������������

���

�����

��������

���������������

�����������

������

�����������

�������������������������

�������

�������

NOTE: Compressor charges for RDCA and

RECA are the same as for Model RCA.

Compressor charges for RDDA and REDA

are the same as for Model RDA.

FIGURE 11 - Compressor Locations

"Bellyband"

Crankcase Heater

FIGURE 10 -

Compressor

Crankcase Heater

 Step 9. Charge the System

When a vacuum of at least 500 microns is reached, close gauge valve,

remove vacuum pump, and break the vacuum using system refrigerant

VAPOR

. LIQUID can be used to break the vacuum if it is connected to

the liquid line ONLY.

Charge the system according to the weights given in the table below. Be

sure to compensate the charge for the addition of the suction line filter

drier. The preferred subcooling should be

18-22°F (10.1-12.3°C) at the liq-

uid line, but may vary based on ambient conditions (See

Step 11).

NOTE : Weighing in the system charge to the specifications will help point

out system faults that may still exist.

IMPORTANT: R407C refrigerant

MUST always be charged as a liquid.

Refrigerant Charge by Model Size

and Compressor for each Circuit

Compressor

Location

(See FIGURE 11)

RCA

RDA

A

B

C

D

Dh*

*

Model

RCA

Model

RDA

Capacity (tons) and Charge (lbs)

Tons Lbs Tons Lbs Tons Lbs Tons Lbs Tons Lbs

25

--

2

5.4

N/A

N/A

N/A

N/A

37

--

3

6.1

N/A

N/A

N/A

N/A

59

--

3

6.1

2

5.1

N/A

N/A

N/A

60

--

3

5.1

2

3.5

N/A

N/A

N/A

77

--

4.5 7.6

2

5.1

N/A

N/A

N/A

78

102

4.5 7.3

2

3.7

N/A

N/A

2

3.4

90

114

4.5 7.3

3

5.1

N/A

N/A

2

3.4

108

126

6.2 8.7

3

5.1

N/A

N/A

2

3.4

109

--

6.2 8.9

3

6.2

N/A

N/A

N/A

120

144

6.2 8.7 4.5 7.3

N/A

N/A

2

3.4

139

--

4.5 8.3 4.5 7.3

N/A

3

6.0

N/A

164

--

6.2 8.7 4.5 7.3

N/A

3

5.1

N/A

166

188

4.5 8.2 6.2 9.2

3

5.8

N/A

2

3.4

184

220

4.5 6.8 6.2 8.5 4.5 6.8

N/A

3

4.5

198

234

4.5 7.5 6.2 9.5 6.2 9.5

N/A

3

4.5

176

230

4.5 7.6

10 14.5

N/A

N/A

3

9.2

226

280

12 tons / 19 lbs

6.2 9.5

N/A

3

9.2

292

346

12 tons / 27.8 lbs

12

9.5

N/A

3

9.2

374

446

10 15.6 10 15.6 10 15.6

N/A

3

10.1

428

10 15.6 10 15.6 10 15.6

N/A

3

10.1

Compressor

Location

(See FIGURE 11)

RCA

RDA

A

B

C

D

Dh*

*

* Reheat pump compressor

Model RCA with

Option AU25

Capacity (tons) and Charge (lbs)

Tons Lbs Tons Lbs Tons Lbs Tons Lbs

60

3

7.1

2

5.5

N/A

N/A

78

4.5 9.3

2

5.7

N/A

N/A

90

4.5 9.3

3

7.1

N/A

N/A

108

6.2 10.7

3

7.1

N/A

N/A

120

6.2 10.7 4.5 9.3

N/A

N/A

164

4.5 9.3 6.2 10.7

N/A

3

5.1

Compressor

Location

(See FIGURE 11)

RCA with Option AU25

A

B

C

D

Crankcase Heater (FIGURE 10) - The primary cooling

compressor on Sizes 059, 077, 109, and 139 is equipped

with a crankcase heater that must be energized for at least

24 hours before starting the unit or after a power outage of

more than 8 hours.
The belly band type crankcase heater is an external heater

attached to the lower portion of the compressor. These

external band heaters require a ground wire to the unit.