beautypg.com

0 compressor maintenance and replacement (cont'd) – Reznor MAPSII Series REDA Users Manual User Manual

Page 18

background image

Form O-MAPS II, P/N 209179 R7, Page 18

 Step 10. System Startup

Assure voltage to compressor does not drop below minimum allowable

voltage (eg. 187 volts for 230/208-3-60, 415 volts for 460/3/60, 518 volts

for 575/3/60) during the period the compressor is trying to start.

If a low

voltage or voltage imbalance condition exists, the electrical problem

must be determined and corrected prior to operating the unit.

Voltage Imbalance - Voltage imbalance is becoming a more common

problem. In a 3-phase system, excessive voltage imbalance between

phases will cause motors to overheat and compressors to fail. Maximum

allowable imbalance is 2%. To determine voltage imbalance, measure and

record the voltage of all three phases. Take the measurements at the com-

pressor terminals with the compressor operating.

Voltage Imbalance Formula:

If the imbalance is within the 2% tolerance, voltage imbalance is not a

problem and the system may be operated. If the imbalance exceeds the

2% tolerance, follow the procedures below.
Solutions to Voltage Imbalance - The cause for a voltage imbalance

problem can originate at the power company or can be caused inside the

building. Try the following on-site solution to determine if the problem can

be easily resolved.

Roll the connections at the compressor terminals one forward. Connect the

wire now on Terminal 1 to Terminal 2, 2 to 3, and 3 to 1. Re-measure and

re-calculate the voltage imbalance. If the imbalance is within 2%, the sys-

tem may be operated.

If the imbalance is not within tolerance, roll the connections one more for-

ward. Re-measure and re-calculate the voltage imbalance. If the imbalance

is within 2%, the system may be operated. If the voltage imbalance still

exceeds 2%, do not start the system. Contact the building owner or person

responsible to have an electrician analyze the buildings's power supply and

load distribution.

 Step 11. Check Superheat and Subcooling

Superheat is the verification that the evaporator coil is properly using the

refrigerant supplied. Too much superheat indicates that the coil is under-

charged. Too little superheat indicates that the coil is overcharged and

potentially flooding liquid refrigerant to the compressor.

Subcooling is the measurement of liquid refrigerant stored in the con-

denser coil. Too much subcooling indicates a system overcharge. Too

little subcooling indicates a system undercharge and may not provide the

thermal expansion valve with a full column of liquid refrigerant for proper

operation.

Two important requirements before checking superheat/subcooling:

1) This unit has fully intertwined refrigerant circuits and each circuit MUST

be isolated before measuring its temperature. Another active circuit will

influence the reading and make it impossible to determine accurate super-

heat and subcooling.

2) If the circuit is equipped with an optional hot gas bypass valve, the valve

must be disabled before measuring superheat and subcooling. Disable

the hot gas bypass valve by removing the cover and adjusting the spring

Compressor

Maintenance

Checklist,

Steps 1-13 (cont'd)

Key:

V1, V2, V3 =

line voltages as measured

VA (average) =

(V1 + V2 + V3)

3

VD =

Line voltage (V1, V2, or V3) that deviates farthest from average (VA)

Formula: % Voltage

Imbalance =

[100 x (VA - VD)]

VA

Saturation

Temperature

Pressure

(psig)

(ºF)

(ºC) R-22 R-407C

0

-17.8

24

19.5

5

-15.0 28.2

23.6

10

-12.2 32.7

28.0

15

-9.4

37.7

32.7

20

-6.7

43

37.9

25

-3.9

48.7

43.6

30

-1.1

54.9

49.6

35

1.7

61.4

56.2

40

4.4

68.5

63.2

45

7.2

76

70.7

50

10.0

84

78.8

55

12.8

92.5

87.5

60

15.6 101.6

96.8

65

18.3

111

106.7

70

21.1 121.4 117.2

75

23.9

132

128.4

80

26.7

144

140.4

85

29.4

156

153.1

90

32.2 168.4 166.5

95

35.0

182

180.8

100

37.8

196

195.8

105

40.6

211

211.8

110

43.3 226.4 228.7

115

46.1

243

246.5

120

48.9

260

265.3

125

51.7 278.4 285.2

130

54.4 296.8 306.1

135

57.2

317

328.2

140

60.0 337.3 351.4

145

62.8

359

375.9

7.0 Compressor

Maintenance

and

Replacement

(cont'd)