0 maintenance requirements (cont'd) – Reznor MAPSII Series REDA Users Manual User Manual
Page 4

Form O-MAPS II, P/N 209179 R7, Page 4
WARNING: Turn off the power before performing all maintenance procedures (except to
check refrigerant pressure and temperature). Lock disconnect switch in OFF position. If the
system has a heat section, when you turn off the power supply, turn off the gas. See Hazard
Levels, page 3.
NOTE: If replacement parts are required, use only factory-authorized parts.
For information, call 800-695-1901 or go to www.RezSpec.com
Models RDCA & RDDA with a gas-fired heat section (beginning of the
heating season) - See Paragraph 9.:
NOTE: If equipped with an optional Model JHUP curb duct furnace,
these same maintenance procedures apply to the duct furnace.
Clean all dirt and grease from the combustion air openings and venter
assembly.
Check the burner and heat exchanger for scale, dust, or lint accumulation.
Clean as needed.
Check the gas valves to ensure that gas flow is being shutoff completely.
Models RECA & REDA with an electric heat section (beginning of the
heating season) - See Paragraph 10.
Check the wiring connections.
Check the heat section and elements for dust or lint accumulation. Care-
fully clean as needed.
2.0 Maintenance
Requirements
(cont'd)
Maintenance
Schedule (cont'd)
TUBING SECTION
• Low Refrigerant Pressure Cutouts
• High Refrigerant Pressure Cutouts
• Filter Driers
• Liquid Line Service Gauge Ports
COMPRESSOR SECTION
• Ckt A Compressor
• Ckt B Compressor
• Ckt C Compressor
• Discharge & Suction Service Ports
• Optional Hot Gas Bypass Valve(s)
HIGH VOLTAGE ELECTRICAL
COMPARTMENT
1) Blower Motor Contactor or Starter
2) Control Transformers (as required)
3) Dehumidification Compressor
Contactor (RDA, RDDA, REDA)
4) Condenser/Compressor Contactor
5) Optional Phase Loss/Phase Rever-
sal Control (optional beginning
10/05; standard prior to 10/05)
6) Optional Damper Motor
Transformer
7) Optional Over/Under Voltage
Control
8A&B) Condenser Motor Capacitors
9) Optional Convenience Outlet
(requires separate supply line)
AUXILIARY COMPARTMENT
10) Digital Controller (FX05 or FX06)
• Optional Damper Motor
• Outside Air Relative Humid-
ity Transmitter (Std RDA/
RDDA/REDA; Optional
RCA/RDCA/RECA)
Models RDCA & RDDA With Gas
Heat Section (FIGURE 1A only):
21) Venter Assembly
22) Single-Stage Gas Valves
23) Optional Modulating Gas Valve
24) Optional Low Gas pressure
Switch
25) Optional High Gas Pressure
Switch
Models RECA & REDA With
Electric Heat Section (FIGURE
1B only):
26) Fuse Block/Fuses
27) Contactor
28) Low Voltage Terminals
29) Manual Reset Limit
30) Auto Reset Limit
FIELD INSTALLED
• Discharge Air Sensor (supply duct)
• Optional Return Air Firestat (duct)
• Optional Discharge Air Firestat
(duct)
• Optional Smoke Detector (duct)
• Optional wall-mounted controls
11) Air Proving Pressure Switch
12&13) Optional Control Relays
14) Optional Dirty Filter Switch
15) Optional Time Clock or BAS Card
16) Humidity Input Converter
Models RDCA & RDDA With Gas
Heat Section (FIGURE 20 only):
17) Combustion Air Pressure Switch
18) Ignition Control
19) Optional Power Signal Converter
20) Venter Motor Capacitor (line
voltage)
BLOWER SECTION
• Blower Motor
Models RDCA & RDDA With Gas
Heat Section (FIGURE 1A only):
• Limit Control (capillary type)
COIL SECTION
• Evaporator Coils
• Thermal Expansion Valves
• Froststat (one per cooling circuit)
• Optional Subcooling Valves
(RCA/RDCA/RECA)
FILTER AND INLET AIR
SECTION
• Inlet Air, Humidity, & Override
Sensors
• Ckt D or Dh Compressor