0 dimensions and clearances (cont'd), 0 mounting, 1 dimensions (cont'd) – Reznor HRPD (Outdoor Duct Furnaces) Unit Installation Manual User Manual

Page 6: 2 clearances, Learances, Figure 2b - dimensions, model series hrpd, Required c, Weights

background image

Form I-RP/HRPD, P/N 132210 R14, Page 6

A

D - Mounting

3-9/32” (83mm)

4-1/16”

103mm

4-1/16”

103mm 2-1/2”

64mm

Alernate

Thermostat

Connection

Alternate

Electric

Connection

1/4” (6mm) dia.

Condensate

Drain (4)

per side

1/2”

13mm

Approx Location of Gas Connection

(for size see Techical Table)

15/16”

24mm

1-1/8”

29mm

1-1/8”

29mm

16-1/4”

413mm

Thermostat

Connection

Electric

Connection

C

3/4”

19mm

3/4”

19mm

G

10-9/16”

268mm

18”

457mm

8-15/32”

215mm

38-17/32”

979mm

3/4”

19mm

3/4”

19mm

LEFT SIDE VIEW

FRONT VIEW

REAR VIEW

TOP VIEW

B

50-1/4”

1280mm

18-3/32”

460mm

AIR

FLOW

1/2”

13mm

52” (1321mm)

51” (1295mm) - Mounting

15/16”

24mm

AIR

FLOW

4.0 Dimensions and Clearances (cont'd)

4.1 Dimensions (cont'd)

FIGURE 2B - Dimensions, Model Series HRPD

Dimensions (inches)

Dimensions (mm)

Size

A

B

C

D

E

Size A

B

C

D

E

250 30-15/16 28-1/2 15-1/4 20-5/16 3-3/32 250 786 724 387 516 79

300 36-7/16

34

20-3/4 25-13/16 1-21/32

300 926 864 527 656 42

350 36-7/16

34

20-3/4 25-13/16 1-21/32

350 926 864 527 656 42

400 41-15/16 39-1/2 26-1/4 31-5/16 1-21/32 400 1065 1003 667 795 42

500 50-3/16 47-3/4 34-1/2 39-9/16 1-21/32 500 1275 1213 876 1005 42

600 50-3/16 47-3/4 34-1/2 39-9/16 1-21/32 600 1275 1213 876 1005 42

700 55-11/16 53-1/4

40

45-1/16 1-21/32

700 1414 1353 1016 1145 42

800 61-3/16 58-3/4 45-1/2 50-9/16 1-21/32 800 1554 1492 1156 1284 42

4.2 Clearances

Clearance to combustibles is defined as the minimum distance from the heater to a

surface or object that is necessary to ensure that a surface temperature of 90°F above

the surrounding ambient temperature is not exceeded.
Clearance is also required to sides of furnace for service.

Required C

learances

Models

Top

Sides*

Bottom

Control

Opposite

Controls

To

Combustibles

To Non-

Combustibles

RP, HRPD

Series

inches 36

Width of furnace plus 6

6

0

0

mm 914

Width of furnace plus 152

152

0

0

* Provide clearance as shown for safety, for combustion air, and for service.

5.0 Mounting

Before installing the furnace, check the supporting structure to be used to verify that it

has sufficient load-carrying capacity to support the weight of the unit. Lifting holes are

provided at each of the four corners of the mounting support rails. Use spreader bars

when lifting to prevent chains or cables from damaging the cabinet. Furnaces must be

level.

Weights

Model

Approximate Net Wt (lbs)

Approximate Net Wt - kg

RP by

Size

125 150 175 200 225 250 300 350 400 125 150 175 200 225 250 300 350 400
201 217 217 247 247 295 295 333 361

91

98

98

112

112 134 134 151 164

HRPD by

Size

250 300 350 400 500 600 700 800

250 300 350 400 500 600 700 800

402 434 434 494 590 590 666 722

182 196 196 224 268 268 302 328

Mounting Models RP, HRPD - These furnaces may be placed directly on a slab or

roof where support is adequate. Support rails provide required clearance from combus-

tibles. See mounting requirements in

FIGURE 3.