beautypg.com

4 typical wiring diagrams, Control wiring – Reznor HRPD (Outdoor Duct Furnaces) Unit Installation Manual User Manual

Page 15

background image

Form I-RP/HRPD, P/N 132210 R14, Page 15

FIGURE 11A - Power-Vented Furnace with Standard Single-Stage Gas

Valve, W.D. 274956

& CAPACITOR

VENTER MOTOR

L1

F

L2

8

10

12

1

2

4

11

2

Y

Y

W

BK

Y

W

BL

R

BK

BK

BK

7

7

7

BK

BR

25

H

TD

H

BR

BR

W

24

H

TD

H

BR

7

BK

BL

W

TIME DELAY

RELAY COIL

12 - 29

22

FAN TD

HEATER

CR

22

7

BLOWER

RELAY COIL

CUSTOMER'S

24 VOLT

8 VA. MAXIMUM

TERMINAL BLOCK --

HEATER COMPARTMENT

1, 2, 4, 7, 8, 10,

WHITE - W

PURPLE - PR

BLUE - BL

GREEN - G

YELLOW - Y

ORANGE - O

RED - R

BROWN - BR

BLACK - BK

WIRING CODE

TOTAL WIRE MINIMUM RECOMMENDED

LENGTH WIRE SIZE

150 FEET #18 GA.

250 FEET #16 GA.

350 FEET #14 GA.

FIELD CONTROL WIRING

BK

8

BK

Y

BR

7

BL

LINE/1/60

GRD

G

40 VA. CONTROL

TRANSFORMER

BK

Y

BL

BR

R

UNIT AUTOMATIC

LIMIT CONTROL

SWITCH

PRESSURE

COMBUSTION

NC
NO

COM

LINE VOLT

24V

11, 12, F, L1 & L2

RP SERIES AH2 OR AH3-AG1-CL1 WD # 274956 REV. #1

OPTIONAL FIELD WIRING

OPTIONAL FACTORY WIRING

FACTORY WIRING

FIELD WIRING

Y

8

SET ANT. AT 1.0 AMPS

OPT. SINGLE STAGE

THERMOSTAT

R

W

OPERATING SEQUENCE

- SET THERMOSTAT AT LOWEST SETTING.

- TURN ON POWER AND MANUAL GAS VALVE TO UNIT.

- SET THERMOSTAT AT DESIRED SETTING.
- FIRING RATE IS CONTROLLED BY THE SINGLE STAGE THERMOSTAT.
- BLOWER MOTOR OPERATES FROM FAN TIME DELAY.

REDUND

ANT

GAS V

AL

VE

AL

TERNA

TE

W

.R. OR R

OBER

TSHA

W

BL

P

BK

BR

M

AIN

PIL

O

T

M

C

PV

PIL

O

T

MV

PV-MV

M

AIN

REDUND

ANT

GAS V

AL

VE

HONE

Y

WELL

CONTACTS

FAN TD

1

3

(SEE NOTES)

DISCONNECT SWITCH

BK

ON 115/460V. UNITS THE CONTROL TRANSFORMER IS A SINGLE VOLTAGE PRIMARY.

- ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.

- USE #14 GA. WIRE FOR LINE AND MOTOR WIRING ON THREE PHASE UNIT.

TO PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.

- LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SIZE SHOULD BE OF A SIZE

A TEMPERATURE RATING OF AT LEAST 105 DEGREES C., EXCEPT FOR ENERGY

MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING

- CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE

- DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED

- THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT:

- THE FOLLOWING CONTROLS ARE SUPPLIED BY REZNOR FOR FIELD INSTALLATION:

FOR 115/460V. UNITS USE BLACK AND YELLOW LEADS.

FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW).

FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).

THERMOSTAT

CUTOFF OR SENSOR LEAD WIRE WHICH MUST BE 150 DEGREES C.

- USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.

BY OTHERS: BLOWER RELAY

NONE

NOTE

USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25

TIMES THE MAXIMUM TOTAL INPUT AMPS.

- WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH

- DISCONNECT SWITCH IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS AN OPTION.

FIRING SEQUENCE:

- ON A CALL FOR HEAT BY THE THERMOSTAT.

- THE VENTER MOTOR IS ENERGIZED AFTER A 15 SECOND (APPROX.)

TIME DELAY.

- VENTER FLOW SWITCH SWITCHES FROM N.C. TO N.O. CONTACTS ENERGIZING

FLAME ON EACH OPERATING CYCLE. THE SENSING PROBE PROVES THE

PRESENCE OF THE PILOT FLAME AND ENERGIZES THE SAFETY SWITCH

PORTION OF THE CONTROL. THE SWITCH ACTION DE-ENERGIZES THE

SPARK GAP AND ENERGIZES THE MAIN VALVE. THE MAIN GAS IGNITES

AND UNIT FIRES AT FULL RATE.

THE PILOT GAS VALVE AND SPARK GAP TO PRODUCE A PILOT

Y

BL

IGNITION

CONTROLLER

PROBE

GND

SPARK

FLAME SENSING

MV/PV

MV

SENSE

TH

PV

24V GND

BR

GND BURNER

G

UNIT CHASSIS

GROUND

6

7

8

9

10

11

12

19

20

21

22

23

24

25

26

27

28

29

30

31

32

13

- IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,

THE SAFETY SWITCH CLOSES THE MAIN VALVE. IF THE PILOT IS

NOT ESTABLISHED WITHIN 120 SEC. THE UNIT LOCKS OUT FOR

ONE HOUR, UNLESS IT IS RESET BY INTERRUPTING POWER TO

THE CONTROL CIRCUIT. (SEE LIGHTING INSTRUCTIONS)

M1(4)

M2(5)

RELAY CONTACTS

VENTER TIME DELAY

M3(1)

M4(3)

VENTER TIME DELAY

RELAY CONTACTS

7.4 Typical Wiring

Diagrams

Field Control Wiring - Length and Gauge

Total Wire

Length

Distance from

Unit to Control

Minimum Recommended

Wire Gauge

150ft (46M)

75ft (23M)

#18 gauge

250ft (76M)

125ft (38M)

#16 gauge

350ft (107M)

175ft (53M)

#14 gauge

Control

Wiring

This manual is related to the following products: