Converting Model RP Duct Furnace for Lower Temperature

Rise and Higher CFM Application

WARNING

This conversion shall be done by a qualified service agency in accordance with the

manufacturer’s instructions and all applicable codes and requirements of the authority

having jurisdiction. If the information in these instructions is not followed exactly, a

fire, explosion or production of carbon monoxide may result causing property damage,

personal injury or loss of life. The qualified service agency performing this work assumes

responsibility for the conversion of this appliance to provide for higher CFM.

WARNING

The instructions in this sheet are designed to prepare a Reznor

®

duct furnace for increased

air throughput conversion prior to installation. If your duct furnace is installed, for your

safety, turn off the gas and the electric before servicing.

NOTE: If airflow is being

reversed or other field-

installed options apply,

refer to the information

in Paragraph 3.2 before

performing this conversion.

FIGURE 22 - Fill in the

Information on the

Conversion Label

Description/Application

2. Remove the Heat Exchanger Baffles - Refer to FIGURE 23 and identify the air baffles

to be removed. Remove the screws from the support brackets and slide the entire

baffle assembly out of the heat exchanger. Reinstall the screws to plug the holes.

This Reznor

®

duct furnace was factory assembled with the air throughput range listed

on the rating plate. The conversion in these instructions will change the air throughput

range as specified in the table below.

Model and

Size

High Air Throughput (CFM)

MAXIMUM

MINIMUM

RP 125

4605

1225

RP 150

5530

1475

RP 175

6450

1720

RP 200

7370

1965

RP 225

8295

2210

RP 250

9215

2455

RP 300

11060

2945

RP 350

12900

3440

RP 400

14745

3930

Verify the size on the heater rating plate. After confirming that the conversion is appro-

priate for the unit, follow the instructions.
1. Fill in the Field Conversion Label - Remove the conversion label, P/N 263310,

from the literature bag. Complete the information.

(date)

(name & address of company making this conversion)

263308

APPENDIX

Instructions