beautypg.com

Combustion air pressure switch setting, Sensor location, Wiring and service – Reznor HRPD (Outdoor Duct Furnaces) Unit Installation Manual User Manual

Page 21

background image

Form I-RP/HRPD, P/N 132210 R14, Page 21

RP with AG39

or AG40

HRPD with

AG41 or AG42

Startup

Cold

Equilibrium at

Full Rate

Factory Setting

Sizes 125-225 Sizes 250 - 400 -1.3" w.c.±0.2 -1.05" w.c.±0.1 -0.58" w.c.±0.05
Sizes 250-400 Sizes 500 - 800 -1.2" w.c.±0.2 -0.95" w.c.±0.1 -0.58" w.c.±0.05

Combustion Air

Pressure Switch

Setting

This uniquely designed modulation system requires combustion air pressure settings

different from the standard system. The approximate settings for the combustion air

proving switch at sea-level operation are:

Calculate the Setpoints with Two Furnace Sections

- Use the following formulas to calculate the controller

settings for Heat Stage 2 and Heat Stage 3 in a system

with two furnace sections.

T

SP

= Setpoints of Heat Stage Controllers (T

SP2

and T

SP3

)

T

SA

= Desired Supply Air Temperature

T

D

= Design (minimum) Entering Air Temperature

Formulas for two furnace sections:

Setpoint for Heat

Stage 2: T

SP2

= T

SA

- 0.46 (T

SA

- T

D

)

Setpoint for Heat

Stage 3: T

SP3

= T

SA

- 0.73 (T

SA

- T

D

)

Set Heat Stage

Controllers - applies

to HRPD with Option

AG41 or AG42

Model HRPD units with Option AG41 and AG42 have “heat stage controllers” that

control operation of the "two-stage" furnace based on outside air temperature

setpoints. Proper setpoints are important to ensure the modulating furnace ("Heat

Stage 1") is always in control and avoids cycling

. The proper setpoint for each

controller must be determined from basic design information. Follow the steps and

example to determine appropriate setpoints. Follow the instructions to locate and set

the controllers.

EXAMPLE : 3600 CFM, Power vented, 100%

Outside Air, -10°F Outdoor Winter Design, 75°F

Desired Supply Air

T

SP2

= 75

- [.46 x (75

- (-10))] = 75 - (.46 x 85) =

35.9
T

SP3

= 75

- [.73 x (75

- (-10))] = 75 - (.73 x 85) =

12.9
Set Stage Heat #2 Controller to 36°F
Set Stage Heat #3 Controller to 13°F

Locate and Set the

Heat Stage Controllers

1. In the inlet air section, locate the heat stage controllers. The same type of

controller may also be used as the optional high ambient limit control (Option

BN2) and as the mixed air controller that is part of air control Options AR12, AR13,

AR15, and AR16). Identify the controllers marked Heat #2 and Heat #3.
2 Furnaces (Model HRPD) - Identify controllers marked Heat #2 and Heat #3 .

2. Adjust each controller to the setpoint as determined in the calculation.

Sensor Location

The duct temperature sensor and mixing tube are shipped loose for field installation

in the dicharge duct. See Paragraph 6.3.5 for instructions on locating the sensor in

the ductwork.
The sensor for Opiton AG40 and AG42 is field suppleid. Follow the guidelines in Para-

graph 6.3.5 and the manufacturer's instrucitons.

the gas pressure to 1.1" w.c., the primary gas pressure switch in the manifold activates

the gear motor that controls the bypass damper in the venter/combustion air system.

The bypass damper opens diverting some of the incoming air directly into the flue duct,

reducing airflow through the burner. Safety switches monitor the position of the bypass

damper. When the gas pressure increases above 1.1" w.c., the bypass damper closes.

Wiring and Service

For wiring, consult the wiring diagram attached to the furnace. All wires in the

electrical box connecting the modulation controls must have a temperature rating of

150°C.

This is a unique system which includes custom-built components and custom settings.

If service is required, follow the general troubleshooting guide on page 28 and the

special troubleshooting guide on page 22.

Computer Controlled

Electronic Modulation

between 20-28%,

Options AG40 and

AG42

The heater functions and is equipped in the same way as for Option AG39 except that

with computer control the temperatures are selected through the field-supplied soft-

ware and there is no temperature selector or duct sensor.

With this option the furnace is equipped with a Maxitrol signal conditioner (

FIGURE

14B) which accepts an input signal of either 4-20 milliamps or 0-10 volts from a cus-

tomer-supplied control device such as a computer. With the dip switches on the condi-

tioner in the "on" positions, the conditioner accepts a 4-20 milliamp signal. In the "off"

positions, the conditioner accepts a 0-10V signal. The conditioner converts the signal

to the 0 to 20 volt DC current required to control the modulating valve.

This manual is related to the following products: