1 fan control, 4 typical wiring diagrams (cont'd) – Reznor HRPD (Outdoor Duct Furnaces) Unit Installation Manual User Manual

Page 16

background image

Form I-RP/HRPD, P/N 132210 R14, Page 16

FIGURE 11B - Power-Vented Furnace with Optional Two-Stage Gas Valve, W. D. 274996

RELAY CONTACTS

1

3

TIME DELAY

& CAPACITOR

VENTER MOTOR

L1

F

L2

8

10

12

1

2

RELAY CONTACTS

4

5

TIME DELAY

4

11

2

Y

Y

W

BK

Y

Y

W

BL

R

BK

BK

BK

7

7

7

BK

BR

20

H

TD

H

BR

BR

W

19

H

TD

H

BR

7

BK

BL

W

TIME DELAY
RELAY COIL
12 - 24

17

FAN TD
HEATER

CR

17

7

BLOWER RELAY COIL

CUSTOMER'S 24 VOLT

8 VA. MAXIMUM

TOTAL WIRE MINIMUM RECOMMENDED
LENGTH WIRE SIZE
150 FEET #18 GA.
250 FEET #16 GA.
350 FEET #14 GA.

FIELD CONTROL WIRING

BK

8

13

R

R

LOW STAGE

PILOT

HIGH STAGE

BK

Y

BR

7

BL

R

W2

TWO

ST

A

GE THERMOST

AT

SET ANT

. A

T 1.0 AMPS

W1

DISCONNECT SWITCH

LINE/1/60

GRD

G

40 VA. CONTROL

TRANSFORMER

BK

Y

BL

BR

R

OPERATING SEQUENCE
- SET THERMOSTAT SWITCH AT "OFF" POSITION.
- TURN ON POWER, MAIN AND PILOT MANUAL GAS VALVES.
- SET THERMOSTAT SWITCH AT "AUTO" POSITION.
- FIRING RATE IS CONTROLLED BY THE TWO STAGE THERMOSTAT.

- SET CONTROL SWITCH AT "OFF" POSITION FOR SHUTDOWN.

UNIT AUTOMATIC

LIMIT CONTROL

SWITCH

PRESSURE

COMBUSTION

NC

NO

COM

LINE VOLT

24V

TERMINAL BLOCK --
HEATER COMPARTMENT

1, 2, 4, 7, 8, 10, 11,

12, 13, F, L1 & L2

OPTIONAL

- BLOWER MOTOR OPERATES FROM FAN TIME DELAY.

RP SERIES
AH2 OR AH3-
AG2-CL7
WD # 274996

HIGH

STG

HI

PV

PIL

O

T

STG

LO

W

C

MV

REDUNDANT

GAS V

AL

VE

HONE

Y

WELL T

WO

ST

A

GE

PIL

O

T

AL

TERNA

TE

W

.R.

T

WO

ST

A

GE

REDUNDANT

GAS V

AL

VE

R

BL

3

HIGH

STG

4

BK

STG

2

LO

W

1

BR

- BLOWER MOTOR REMAINS ON AS DETERMINED BY FAN TIME DELAY.

CONTACTS

FAN TD

1

3

(SEE NOTES)

BK

GREEN - G

WHITE - W

PURPLE - PR

BLUE - BL

YELLOW - Y

ORANGE - O

BROWN - BR

BLACK - BK

WIRING CODE

RED - R

FIELD WIRING

FACTORY WIRING

OPTIONAL FACTORY WIRING

OPTIONAL FIELD WIRING

ON 115/460V. UNITS THE CONTROL TRANSFORMER IS A SINGLE VOLTAGE PRIMARY.

- ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.

- USE #14 GA. WIRE FOR LINE AND MOTOR WIRING ON THREE PHASE UNIT.

TO PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.

- LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SIZE SHOULD BE OF A SIZE

A TEMPERATURE RATING OF AT LEAST 105 DEGREES C., EXCEPT FOR ENERGY

MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING

- CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE

- DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED

- THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT:

- THE FOLLOWING CONTROLS ARE SUPPLIED BY REZNOR FOR FIELD INSTALLATION:

FOR 115/460V. UNITS USE BLACK AND YELLOW LEADS.

FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW).

FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).

THERMOSTAT

CUTOFF OR SENSOR LEAD WIRE WHICH MUST BE 150 DEGREES C.

- USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.

BY OTHERS: BLOWER RELAY

NONE

NOTES

USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25
TIMES THE MAXIMUM TOTAL INPUT AMPS.

- WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH

- DISCONNECT SWITCH IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS
AN OPTION.

FIRING SEQUENCE:
- ON A CALL FOR HEAT BY THE LOW STAGE OF THERMOSTAT.
- THE VENTER MOTOR IS ENERGIZED AFTER A 15 SECOND (APPROX.)
TIME DELAY.

- VENTER FLOW SWITCH SWITCHES FROM N.C. TO N.O. CONTACTS ENERGIZING

FLAME ON EACH OPERATING CYCLE. THE SENSING PROBE PROVES THE
PRESENCE OF THE PILOT FLAME AND ENERGIZES THE SAFETY SWITCH
PORTION OF THE CONTROL. THE SWITCH ACTION DE-ENERGIZES THE
SPARK GAP AND ENERGIZES THE MAIN VALVE. THE MAIN GAS IGNITES
AND UNIT FIRES AT LOW RATE.
- ON A CALL FOR HEAT BY THE HIGH STAGE OF THE THERMOSTAT, THE
UNIT FIRES AT FULL RATE.

THE PILOT GAS VALVE AND SPARK GAP TO PRODUCE A PILOT

- IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,
THE SAFETY SWITCH CLOSES THE MAIN VALVE. IF THE PILOT IS
NOT ESTABLISHED WITHIN 120 SEC. THE UNIT LOCKS OUT FOR
ONE HOUR, UNLESS IT IS RESET BY INTERRUPTING POWER TO
THE CONTROL CIRCUIT. (SEE LIGHTING INSTRUCTIONS)

C

7

BL

IGNITION

CONTROLLER

PROBE

GND

SPARK

FLAME SENSING

MV/PV

MV

SENSE

TH

PV

24V GND

BR

GND BURNER

G

UNIT CHASSIS

GROUND

BK

7

8

9

10

11

12

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

13

30

8.1 Fan Control

Service NOTES: To

replace the fan control on

units manufactured prior to

11/04, a replacement kit is

required. Order

P/N 209184.

Prior to 10/03, the fan

control was optional. Check

the wiring diagram on the

furnace.

8.0 Controls

7.0 Electrical Supply and Connections (cont'd)

7.4 Typical Wiring Diagrams (cont'd)

1. A fan control provides for the following control of the field-supplied blower.

(a) After the gas valve opens, there is a time delay of blower operation to prevent

the discharge of cold air.

(b) Blower operation continues after the thermostat is satisfied as determined by

the fan time delay.

2. To be sure that the blower can continue to operate, the power supply to the

furnace

MUST NOT be interrupted except when servicing the unit.

3. If the customer wants the furnace off at night, the gas valve circuit SHOULD

BE OPENED by a single pole switch wired in series with the thermostat. Some

thermostats are provided with this feature. Multiple units controlled from a single

thermostat are shut off in the same manner. For proper operation, be sure the fan

control wiring is observed.