beautypg.com

Potter PFC-6075 User Manual

Page 87

background image

5-81

PFC-6075 • 5403593 • Rev C • 2/13

NAC Functions
The four (4) on-board circuits (NACs 1&2, I/O Ckts 1&2) are automatically configured as “General Purpose”, but may be

reconfigured and renamed. The I/O circuits have additional configuration options since they may be configured as inputs. Refer to

the two (2) tables below for descriptions of the configuration functions.

NAC & I/O Circuit Configuration Functions

Table 18:

Function

Description

Unused

Circuit is unused.

General Purpose

General purpose NAC; obeys zone “output pattern” programming.

Potter Sync

Drives Potter synchronized horns / strobes.

Gentex Sync

Drives Gentex synchronized horns / strobes.

System Sensor Sync

Drives System Sensor synchronized horns / strobes.

Wheelock Sync

Drives Wheelock synchronized horns / strobes.

Aux Constant

Constant DC power.

Aux Resettable

Constant DC power; disconnects power during system reset.

Aux Door Holder

Constant DC power; disconnects when an alarm occurs.

Aux Door Holder Low AC Drop

Constant DC power; disconnects on AC Loss or when an alarm occurs.

Aux ANSI

Always on ANSI pattern used for ASB pattern synchronization.

City Tie

Municipal box connection

I/O Circuit Functions

Table 19:

Function

Description

Input Pull Station

Pull Station Input

Input Water Flow

Water Flow Input obeys water flow delay as defined in “General Options”.

Input Supervisory

Supervisory Input

Input Tamper

Tamper Input reports as supervisory.

Input Fire Drill

Fire Drill Input activates a fire drill.

Input Trouble Monitor

Trouble Input creates a trouble condition.

Input Aux

Aux Input reports as untyped alarm.

Input Abort

Abort Input is used only with releasing applications.

Input Release Follower

Release Follow Input causes immediate activation of release solenoid.

Input Reset

Reset input initiates system reset.

Input Silence

Silence Input initiates system silence.

Trigger IO Reverse Polarity

Reverse Polarity Output report trouble.

Trigger IO Reverse Polarity No Trouble

Reverse Polarity Output report no trouble.