Monitored Output Module – 4 inch mount (MOM-4)
If the power supply connected to the MOM-4 is power limited, then the outputs are power limited. An example of a MOM-4

wired as a conventional application is shown here.

Example of MOM-4 with NAC Connections

Figure 18.

Monitored Output Module

Model No. MOM-4

From FACP or Previous Module

To Next Module

From FACP or Previous Module

To Next Module

24-

24+

S-

S+

A-

A+

SLC Loop

LED

JP1

Select DC

Notification Appliance

5.1KΩ 1/2W EOLR

_

+

_

+

_

+

Output Rating:

24VDC / 2.0A

Analog Sounder Base (ASB)

Example of Analog Sounder Base Wiring

Figure 19.

Notes:

The supply power must be coded in order for the output to be coded.

1.

ASB does not generate a coded output. It will track the pattern delivered to its 24 vDC input.

2.

Analog Relay Base (ARB)

Example of Analog Relay Base Wiring

Figure 20.

DWG #593-18

Analog Sounder Base

Model No. ASB

S-

S+

S+
S-

TB1

24+
24-

S-

S+

SLC Loop

24 VDC-

24 VDC+

From FACP or

Previous Module

SLC Loop

24 VDC+

24 VDC-

To Next Module

DWG #593-19

To Next Module

Analog Relay Base

Model No. ARB

S-

24+

S+

24-

S+
S-

NO2

NO1

NC1

C1(8A)

C2(2A)

NC2

TB1

TB2

SLC Loop

24 VDC+

24 VDC-

From FACP or

Previous Module

SLC Loop

24 VDC+

24 VDC-

LED

NO2

NO1

NC1

C1(8A)

C2(2A)

NC2

TB2

8.0A / 240VAC

8.0A / 30VDC

2.0A / 240VAC

2.0A / 30VDC

DWG #593-20