Analog sounder base (asb) – Potter PFC-6075 User Manual
Page 26
3-20
PFC-6075 • 5403593 • Rev C • 2/13
Monitored Output Module – 4 inch mount (MOM-4)
If the power supply connected to the MOM-4 is power limited, then the outputs are power limited. An example of a MOM-4
wired as a conventional application is shown here.
Example of MOM-4 with NAC Connections
Figure 18.
Monitored Output Module
Model No. MOM-4
From FACP or Previous Module
To Next Module
From FACP or Previous Module
To Next Module
24-
24+
S-
S+
A-
A+
SLC Loop
LED
JP1
Select DC
Notification Appliance
5.1KΩ 1/2W EOLR
_
+
_
+
_
+
Output Rating:
24VDC / 2.0A
Analog Sounder Base (ASB)
Example of Analog Sounder Base Wiring
Figure 19.
Notes:
The supply power must be coded in order for the output to be coded.
1.
ASB does not generate a coded output. It will track the pattern delivered to its 24 vDC input.
2.
Analog Relay Base (ARB)
Example of Analog Relay Base Wiring
Figure 20.
DWG #593-18
Analog Sounder Base
Model No. ASB
S-
S+
S+
S-
TB1
24+
24-
S-
S+
SLC Loop
24 VDC-
24 VDC+
From FACP or
Previous Module
SLC Loop
24 VDC+
24 VDC-
To Next Module
DWG #593-19
To Next Module
Analog Relay Base
Model No. ARB
S-
24+
S+
24-
S+
S-
NO2
NO1
NC1
C1(8A)
C2(2A)
NC2
TB1
TB2
SLC Loop
24 VDC+
24 VDC-
From FACP or
Previous Module
SLC Loop
24 VDC+
24 VDC-
LED
NO2
NO1
NC1
C1(8A)
C2(2A)
NC2
TB2
8.0A / 240VAC
8.0A / 30VDC
2.0A / 240VAC
2.0A / 30VDC
DWG #593-20