Potter PFC-6075 User Manual
Page 83
5-77
PFC-6075 • 5403593 • Rev C • 2/13
Zone Styles
Table 16:
Zone
Description
System Alarm
Used for outputs that will be activated upon any alarm.
System Supervisory
Used for outputs that will be activated upon any supervisory.
System Trouble
Used for outputs that will be activated upon any trouble.
Zone Attributes
Zone attributes are the settings that control the overall behavior of devices within the zone. The zone may be configured as
latching or non-latching, silenceable vs. non-silenceable, among other attributes.
Tips: Double-click in a field to modify an applicable field, i.e., zone name or alarm count. Click in fields with a
selection box to select or deselect the option, i.e., silenceable or latching.
All zones default to an “Alarm” style or type when first created. The figure shown below is an example of the default attributes of
a "Alarm" zone.
Example of Zone Attributes (Fields 1-10)
Figure 102.
Refer to the table below for a brief explanation of zone attributes:
Zone Attributes
Table 17:
Attribute
Description
Zone Name
Default = Zone “x”
(where “x” is a sequential number)
Zone name may be up to sixteen (16) alphanumeric characters.
•y
Alarm Count
Default = 1
Defines the number of inputs that must be in alarm before outputs are
•y
activated.
Default is one (1); up to 10 inputs may be selected.
•y
Silenceable / Non-Silenceable
Default = Silenceable
If zone defined as “
•y
silenceable” allows an operator to silence outputs by
pressing the SILENCE button.
Latching / Non-Latching
Default = Latching
Available for one
•y
(1) count zones only.
Latching zone requires operator to press
•y
Reset.
Non-latching zone will automatically turn off outputs when condition clears.
•y
Local / Non-Local
Default = Non-Local
Used only for “
•y
Report by Zone” option.
Allows a zone to be specified as a non-reporting zone.
•y