P-Link Devices

Accessory devices, such as remote and LeD annunciators, and a remote expander (RLY-5) are connected to the main control

panel utilizing the four-wire P-Link bus for power and communication. This panel supports a maximum of 64 P-Link devices,

which can be connected using a Class B or Class A wiring style (examples are provided throughout this topic).

Note: If you have chosen to install an optional PSN-1000/PSN-1000(e) power expansion board, refer to Section 6:

PSN-1000/PSN-1000(E) – Installing, Operating & Programming, for instructions on installing this appliance.

Configuration Characteristics

P-Link current rating is one (1) amp.

y

y

P-Link voltage rating is 24 vDC.

y

y

The maximum wire length is 6,500 feet.

y

y

Maximum Wire Resistance Formula
The maximum resistance is based on the load placed on the circuit. To calculate the maximum wire resistance, use the following

formula:

(Total Annunciator Alarm Current) x (Wire Resistance) < 6 Volts