beautypg.com

Potter PFC-6075 User Manual

Page 8

background image

1-2

PFC-6075 • 5403593 • Rev C • 2/13

Analog / Addressable Sensing Technology

y

y

Drift Compensation

y

Drift Alert

y

NFPA 72 compliant calibrated smoke test built-in

y

P-Link Accessories

RA-6500 or RA-6075 Remote Annunciator – Maximum of 31 per system in any combination

y

y

UD-1000 Dual Line Fire Communicator – Maximum of 1 per system

y

y

CA-6075 Class A converter module – Maximum of 1 per system allows for Class A wiring of the SLC circuit, P-Link

y

y

communication bus and the two (2) built-in NAC circuits
PSN-1000 / PSN-1000(e) Intelligent Power Supply expander – An accessory to the panel providing ten (10) amps of

y

y

additional power, with four (4) input points, six (6) notification circuits and a P-Link interface
LeD-16 Annunciator module - Maximum of 10 total per system (

y

y

the total may be any combination of LED-16 and

DRV-50 LED modules) allows for up to 16 zones alarm, supervisory and trouble conditions to display, and 5 non-

programmable system LeDs that display system's overall condition
DRv-50 LeD Driver module - Maximum of 10 total per system (

y

y

the total may be any combination of LED-16 and DRV-50

LED modules) allows output to up to 50 LeDs, 4 dry contact inputs, and 5 non-programmable system LeDs that display

system's overall condition
RLY-5 Relay Board module - Maximum of 31 per system provides five (5) Form-C relay outputs

y

y

FCB-1000 Fire Communications Bridge - An accessory that provides a remotely-located IP connection to the panel

y

y

FIB-1000 Fiber Interface Bridge - An accessory to the panel that converts the standard 4-wire P-Link bus to and from optic

y

y

cable capable of Class A operation; maximum of 30 total per system
SPG-1000 Serial Parallel Gateway - An accessory to the panel that allows a serial and/or parallel printer connection;

y

y

maximum of 31 per system

SLC Loop Accessories

Addressable Sensors

Photoelectric Smoke Detector (PSA)

y

Photoelectric/Heat Smoke Detector (PSHA)

y

Fixed Temperature Heat Detector (FHA)

y

Rate of Rise/Fixed Temperature Heat Detector (RHA)

y

Addressable Isolator Base (AIB)

y

Addressable Relay Base (ARB)

y

Addressable Sounder Base (ASB)

y

Addressable Pull Station (APS)

y

Addressable Modules

Miniature Contact Module (MCM)

y

Single Contact Module (SCM-4)

y

Dual Contact Module (DCM-4)

y

Twin Relay Module (TRM-4)

y

Monitored Output Module (MOM-4)

y

Conventional Input Zone Module (CIZM-4)

y

Short Circuit Isolator (SCI)

y