I/o 1 i/o 2, Municipal box connection, Relay output wiring – Potter PFC-6075 User Manual
Page 34

3-28
PFC-6075 • 5403593 • Rev C • 2/13
Municipal Box Connection
When programmed as a municipal box connection, the circuit power is limited, supervised for open and short circuit conditions,
and provides a local energy connection.
Municipal Box Wiring Example
Figure 27.
Notes:
I/O circuits and/or NAC Circuits can be used as Municipal
Box connection .
The EOL device shall be installed in the same electrical enclosure as the Municipal Box.
Panel
Connection
I/O 1 I/O 2
-
+ -
+
Municipal
Box
+
-
End of line device
5.1k ohm 1/2W
Part #3005012
Notes:
The trip current for NAC1 and NAC2 is three (3) Amps, and one (1) Amp for I/O1 and I/O2.
1.
The maximum voltage rating is 24 vDC.
2.
The panel has ground fault detection on municipal box connection circuits. The impedance to ground for ground fault
3.
detection is 0 ohms.
Relay Output Wiring
The panel has three (3) dedicated common relays. The dedicated trouble relay is a fail safe trouble relay that changes position
anytime a trouble condition occurs.
Relays have a contact rating of 24vDC / 3.0A, 125vAC / 3A, and Power Factor of 1.0. These outputs are non-power limited and
not supervised.
Note: If the power supply connected to the devices is power-limited, then the outputs are power limited.
Relay Outputs
Figure 28.
TROUBLE
NC COM NO
SUPERVISORY
NC COM NO
ALARM
NC COM NO
DWG #602-9A
DWG #593-26