Lever type bleeder valve – Potter Releasing Systems User Manual
Page 68

68
BVL
LEVER TYPE BLEEDER VALVE
PRINTED IN USA
PAGE 1 OF 1
MFG. #5400799 - REV K
5/08
General Information
The Model BVL, lever type bleeder valve, is for use as a test valve for
pressure operated devices on wet pipe sprinkler systems that have excess
pressure, or dry pipe sprinkler systems.
The BVL should be installed in-line with the pressure device. It provides
a convenient means for removal or testing the pressure actuated device
without affecting the pressure in the system. Closing the valve (moving
the valve handle perpendicular to the 1/2" pipeline) shuts off the water
or air from the supply and opens a small orifice (pin-hole) to exhaust the
pressure between the valve and the pressure device. This should provide
a low pressure actuation of the pressure device, testing its operation.
Installation
The BVL should be installed in-line to the alarm or supervisory device
with the “PD” (Potter Device) stamp, or with the arrow pointing toward
the alarm or supervisory device that is to be tested.
Valve Body: Bronze
Handle: Zinc plated steel
Maximum Pressure: 300 PSI (20.7BAR)
Connections: 1/2" NPT
Exhaust Orifice: .125" (3mm)
Stock number - 1000018
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada: 888-882-1833
• www.pottersignal.com
PS40
BVL
RISER TO SPRINKLERS
DWG# 799-1
The BVL should be installed so the exhaust orifice is pointed in a
safe direction.