beautypg.com

Potter Releasing Systems User Manual

Page 42

background image

42

Semi-annually

Check cold weather valves (if provided) in the Fall, before freezing weather.

The valves should be closed and that portion of the system drained. In the

Spring, as soon as freezing weather has passed, the cold weather valve should

be reopened.

Note: Cold weather valves are sometimes used to isolate a portion of a

sprinkler system that might be subject to freezing temperatures. During

cold weather, the valve is closed and that portion of the system is drained.

However, cold weather valves are not desirable, as protection is not provided

during cold weather or if valve is inadvertently left closed. Also, NFPA 13

does not recognize cold weather valves. A preferred arrangement would be

to provide a dry pipe system in the unheated area, or an antifreeze loop in a

small area.

Pipe Blockage

It is important that the sprinkler system piping be maintained free of obstructions,

so, periodically, sprinkler systems — including valves and piping — should be

examined internally. Where unfavorable conditions such as those listed below are

found, the systems should be examined for blockage immediately, and at five-year

intervals thereafter. Look for:

A. Defective screens at pump intakes where pumps take suction from

streams, ponds or lakes. Failure of the screens might allow debris into the

pump suction and into the system piping.

B. Debris and obstructive material discharged during routine water tests, such

as from hydrant water flow tests or 2-inch main drain tests.

C. Debris found in dry-pipe valves, check valves and fire pumps during

maintenance.

D. Heavy discoloration of water during 2-inch drain tests, or plugging of the

inspector’s test connections.

E. Plugged piping, which is found during system alterations or after system

failure during fires.

F. Failure to flush underground mains following installation or repairs.

Debris might have been left in the piping during construction.

G. A record of broken water mains in the area. Repair of these broken pipes

could have introduced debris into the system.

Tests Tests are required at various frequencies as noted below. Use the Inspection Forms at the end of this

chapter to record all test results.

Quarterly

All Sprinkler Systems:

Flow test main drains.

This involves noting and recording the pressure of the gauge on the

lower side of the sprinkler valve (Figure 2-2 above). (This is the static water

supply pressure.) Open the 2-inch main drain fully; after the

flow has stabilized, note and record the pressure on the gauge again.

(This is the residual water supply pressure.) If the pressure readings vary

significantly from those readings previously recorded, there is indication

that something may be wrong with the water supply — such as a closed

valve or blocked pipe. Loss of pressure of more than 10 percent should

This manual is related to the following products: