Sprinkler system supervision includes – Potter Releasing Systems User Manual
Page 14

14
Determine Fire Alarm Requirements
NFPA 101 Life Safety Code determines the fire alarm requirements based on the occupancy rating of the building.
Within each occupancy chapter, section 3.4 will specify the fire alarm requirements for that occupancy class.
Section 3.4 is “Detection, Alarms & Communication”. Section 3.5 is “Extinguishing Requirements”.
Section 3.4 Detection, Alarms and Communication
The General Provision
Specifies the conditions under which a fire alarm is required in that particular occupancy.
The Initiation Provision
Specifies how the fire alarm will be activated, other than as relates to automatic fire detection. It is typical in
many occupancy chapters that the Initiation provision call for “Manual activation in accordance with 9.6.2.1”.
When referred to chapter 9, only the applicable portions of chapter 9 apply for that occupancy.
The Notification Provision
Specifies “On Premises” signaling requirements. It may require voice evacuation, and may permit or prohibit
the use of “Pre-Signal” features.
The Detection Provision
Specifies requirements for automatic detection.This section should always be reviewed, even if the building is
not required to have a fire alarm system under the general statement for that occupancy class.
The Emergency Forces Notification Provision
Includes any requirement for “Off Premises” signaling (monitoring).
Section 3.5 Extinguishing Requirements
Specifies requirements for automatic sprinkler systems. Refers to chapter 9 section 9-7 “Automatic Sprinklers
and other Extinguishing Equipment”
The code may require either an, approved automatic sprinkler or an approved supervised automatic sprinkler.
Where a supervised automatic sprinkler is required, NFPA 101 2009 9-7.2.1 and 9-7.2.2 are applicable.
Sprinkler System Supervision Includes:
Water flow
Water Supply Control Valves
Fire Pump Status
Water Tank, Levels and Pressures
Air Pressure on Dry Pipe Systems
Building Temperature
Water supply control valves shall be supervised to obtain a distinctive signal when in an off normal position,
within 2 revolutions of the handwheel, or when the valve has moved one fifth from its normal position.
The switch shall not restore to a normal condition throughout the entire travel of the valve, until it is restored to
a fully open position.
A Supervisory signal must be visually or audibly distinctive from both Alarm and Trouble signals.
Water flow and supervisory devices cannot be connected on the same initiating circuit so that the closing of a
valve is annunciated as a “trouble” condition.