Appendix B: Reporting codes
NX-8E Control Panel Installation Manual
81
Loc. Description
Default
Setting
43
Go to program code and authorization
Segment 1
1 = Reserved
2 = Enable go to program code as an arm only code
3 = Enable go to program code as an arm only after
closing
4 = Enable go to program code as a master
arm/disarm code (can change user code)
5 = Enable go to program code as an arm/disarm
code
6 = Enable go to program code to bypass zones
7 = Enable go to program code opening and closing
reports
8 = Reserved
Segment 2
1 = Enable go to program code for partition 1
2 = Enable go to program code for partition 2
3 = Enable go to program code for partition 3
4 = Enable go to program code for partition 4
5 = Enable go to program code for partition 5
6 = Enable go to program code for partition 6
7 = Enable go to program code for partition 7
8 = Enable go to program code for partition 8
44
Duress code
15, 15, 15, 15, 15, 15
45
Auxiliary outputs 1 to 4 partition selection
Segment 1 = Output 1 partitions
1
2
3
4
5
6
7
8
Segment 2 = Output 2 partitions
1
2
3
4
6
6
7
8
Segment 3 = Output 3 partitions
1
2
3
4
5
6
7
8
Segment 4 = Output 4 partitions
1
2
3
4
5
6
7
8
46
Auxiliary outputs 1 to 4 special timing
Segments 1 to 4 (outputs 1 to 4)
Output 1
Output 2
Output 3
Output 4
1 = Aux output timed in minutes
1
1
1
1
2 = Aux output to latch
2
2
2
2
3 = Aux output to stop timing upon user code
entry
3
3
3
3
4 = Aux output activates only betw een closing and
opening time
4
4
4
4
5 = Aux output activates only betw een opening and
closing time
5
5
5
5
6 = Invert aux output (0 V going to 12 V w hen
activated)
6
6
6
6
47
Auxiliary output 1 event/times
Segment 1 = Event number for output 1
0 (burglary alarm)
Segment 2 = Timing for output 1
10 (seconds)
48
Auxiliary output 2 event/times
Segment 1 = Event number for output 2
1 (fire alarm)
Segment 2 = Timing for output 2
10 (seconds)
49
Auxiliary output 3 event/times