beautypg.com

Interlogix NX-8E Installation Manual User Manual

Page 85

background image

Appendix B: Reporting codes

NX-8E Control Panel Installation Manual

81

Loc. Description

Default

Setting

43

Go to program code and authorization

Segment 1

1 = Reserved

2 = Enable go to program code as an arm only code

3 = Enable go to program code as an arm only after

closing

4 = Enable go to program code as a master

arm/disarm code (can change user code)

5 = Enable go to program code as an arm/disarm

code

6 = Enable go to program code to bypass zones

7 = Enable go to program code opening and closing

reports

8 = Reserved

Segment 2

1 = Enable go to program code for partition 1

2 = Enable go to program code for partition 2

3 = Enable go to program code for partition 3

4 = Enable go to program code for partition 4

5 = Enable go to program code for partition 5

6 = Enable go to program code for partition 6

7 = Enable go to program code for partition 7

8 = Enable go to program code for partition 8

44

Duress code

15, 15, 15, 15, 15, 15

45

Auxiliary outputs 1 to 4 partition selection

Segment 1 = Output 1 partitions

1

2

3

4

5

6

7

8

Segment 2 = Output 2 partitions

1

2

3

4

6

6

7

8

Segment 3 = Output 3 partitions

1

2

3

4

5

6

7

8

Segment 4 = Output 4 partitions

1

2

3

4

5

6

7

8

46

Auxiliary outputs 1 to 4 special timing

Segments 1 to 4 (outputs 1 to 4)

Output 1

Output 2

Output 3

Output 4

1 = Aux output timed in minutes

1

1

1

1

2 = Aux output to latch

2

2

2

2

3 = Aux output to stop timing upon user code

entry

3

3

3

3

4 = Aux output activates only betw een closing and

opening time

4

4

4

4

5 = Aux output activates only betw een opening and

closing time

5

5

5

5

6 = Invert aux output (0 V going to 12 V w hen

activated)

6

6

6

6

47

Auxiliary output 1 event/times

Segment 1 = Event number for output 1

0 (burglary alarm)

Segment 2 = Timing for output 1

10 (seconds)

48

Auxiliary output 2 event/times

Segment 1 = Event number for output 2

1 (fire alarm)

Segment 2 = Timing for output 2

10 (seconds)

49

Auxiliary output 3 event/times