beautypg.com

Location 206 - auto disarm day selection, Location 207 - serial port selector – Interlogix NX-8E Installation Manual User Manual

Page 59

background image

Chapter 2: Reporting codes

NX-8E Control Panel Installation Manual

55

Location 204
Zones 185 to 192 zone
types

Location 204 has eight segments of numerical data. Use this location
to program the zone type for zones 185 to 192. Use segment 1 for
zone 185, segment 2 for zone 186, etc. The segment defaults are 6,
6, 6, 6, 6, 6, 6, 6.

Location 205
Zones 185 to 192
partition

Location 205 has eight segments of feature selection data. Use this
location to select the partitions (1 to 8) that zones 185 to 192 reside in.
Each segment corresponds to a zone (segment 1 to zone 185,
segment 2 to zone 186, etc.). In each segment, enter 1 for partition 1
through 8 for partition 8.

Location 206 - Auto disarm day selection

Location 206 has one segment of feature selection data. Use this location to
program which days the system autodisarms. If a zone is faulted when the panel
tries to autodisarm, the zone is bypassed.

1 = Sunday

2 = Monday

3 = Tuesday

4 = Wednesday

5 = Thursday

6 = Friday

7 = Saturday

8 = Reserved

Location 207 - Serial port selector

Location 207 has one segment of feature selection data. Use this location to
enable the serial port operations.

0 = Disabled (default)

1 = NX-584 enabled

2 = Serial printer enabled

Locations 208 to 211 - Home automation system

Location 208 - Baud rate

Location 208 has one segment of numerical data.

The NX-584 can operate on a number of different baud rates. Consult the home
automation information to determine the best baud rate for your application and
program it in Location 208. The default is 2 - 9600 Baud or the serial printer baud
rate.

0 = 2400 Baud (2.4K)

1 = 4800 Baud (4.8 K)

2 = 9600 Baud (9.6 K)

3 = 19200 Baud (19.2 K)

4 = 38400 Baud (38.4K)

5 to 7 = Reserved