Rack Temperature Requirements

The operating temperature inside the rack will always be higher than the room
temperature, and is dependent on the configuration of equipment in your rack.
The TMRA for each piece of equipment should be checked before installation.
The maximum internal rack temperature for your configuration should not
exceed the values in the following table:

Table 3-1

Rack Internal Temperature Maximums

Equipment Included

Maximum InternalRack Temperature

Rack-Mountable ProLiant Servers

50°C/122°F

Compaq Rack-Mountable options

40°C/104°F

Other manufacturers' options

See other manufacturers' specifications

CAUTION: To reduce the risk of damage to the equipment
when installing third-party options:

Ensure that the option equipment does not impede airflow to
the Rack-Mountable ProLiant Servers or increase the internal
rack temperature
beyond the Compaq specified maximum rating.

Ensure that the Manufacturer’s Maximum Recommended
Ambient Operating Temperature of the option equipment is
not exceeded when installed in the rack.