N-bus addressing, Profinet setup, Displayed gateway information – Flintec MCS-08 User Manual
Page 45: Profinet data structure
MCS-08 Technical Manual, Rev. 1.04 December 2012
Page 45 of 52
11.3. N-Bus Addressing
MCS-08 modules communicate to each other over the internal N-bus. The MCS-08xx gateway module is the
master of the internal N-bus. All other MCS-08 modules are slaves and have to be addressed to the gateway
module. The N-bus addressing can be done by using the xFace PC software (refer to chapter 5.3) or via setup
switch (refer to chapter 5.8).
11.4. ProfiNet Setup
The ProfiNet setup is done by the xFace software. Connect the gateway module with your PC via the RS-232C
service port on the module as shown in figure 11.2. After connecting the xFace software with the gateway
module select the Gateway tab. The Gateway tab is shown in figure 11.3. It displays all gateway information
and ProfiNet settings.
Figure 10.3
– MCS-08PN gateway setup
You will see the ProfiNet setup in this tab.
ProfiNet Setup
There are 7 setup parameters for ProfiNet network.
DHCP
Dynamic Host Configuration Protocol automates network parameters if it is enabled.
Default is „Disable‟.
Host Name
Enter a unique host name to the instrument.
Default is „ ‟
IP Address
If DHCP is disabled, define IP address manually. Default is „192.168.16.250‟
Default Gateway
If DHCP is disabled, define default gateway manually. Default is „192.168.16.254‟.
Subnet Mask
If DHCP is disabled, define subnet mask
manually. Default is „255.255.255.0‟.
Primary DNS
If DHCP is disabled, define primary DNS manually. Default is „208.67.222.222‟..
Secondary DNS
If DHCP is disabled, define secondary DNS manually. Default is „208.67.220.220‟.
Default password
“123456”
Displayed Gateway Information
External Bus: Profibus DP
Firmware Version / PN Firmware Version: Revision number of the firmware
Firmware Date / PN Firmware Date: Release date of the firmware
Hardware Version: Revision number of the main printed circuit board
Serial Number:
The module‟s serial number
Gateway Status: Indicates the system OK status
MAC Address: The module‟s MAC address.
ProfiNet Data Structure
Please refer to chapter 5.12