MCS-08 Technical Manual, Rev. 1.04 December 2012
Page 30 of 52
*Register address for MCS-08AD [1]: 4
th
…5
th
Dword,
MCS-08AD [2]: 6
th
…7
th
Dword,
MCS-08AD [3]: 8
th
…9
th
Dword,
MCS-08AD [4]: 10
th
…11
th
Dword,
MCS-08AD [5]: 12
th
…13
th
Dword,
MCS-08AD [6]: 14
th
…15
th
Dword,
MCS-08AD [7]: 16
th
…17
th
Dword
Bit no.
3
rd
, 5
th
, 7
th
, 9
th
, 11
th
, 13
th
, 15
th
, 17
th
Dword Description
D31…D16
Not in use
D15…D12
Error
Codes
0111
Module not found
Error Codes of
MCS-08AD
0110
Low/High voltage detetction error
0101
In setup mode
0100
System error
0011
ADC underrange
0010
ADC overload
0001
ADC out
0000
No error found
D11…D10
Not in use
D9
Operation
Mode
0
Weight / Force mode
Status of
MCS-08AD
1
Count mode
D8
Zero
Range
0
Out of zero range
1
In zero range
D7
Indication
0
Gross
1
Net
D6
Motion
Detection
0
Stable
1
Unstable
D5
D4
D3
D2
D1
00000
Indicated weight
Response of 2
nd
Dword description
00001
Gross weight
00010
Tare weight
00011
Indicated weight (floating point type)
00100
Gross weight (floating point type
00101
Tare weight (floating point type)
00110
Increased resolution for indicated weight
10000
Calibration status (refer to table below
D0
Toggles
The command is applied successfully
CMD flag
Bit no.
2nd, 4
th
, 6
th
, 8
th
, 10
th
, 12
th
, 14
th
, 16
th
Dword Description when Read Command is
‘Calibration Status’. Refer to PLC output to MCS-08Px input for 3
rd
Dword
D31…D16
Not in use
D15
D14
D13
D12
D11
D10
D9
D8
Error
Codes
0000 0001
Calibration timeout
- Restart calibration
Calibration Status
of MCS-08AD
0000 0010
ADC error
- Re-energize the module
0000 0011
Module can not be calibrated
- Load cell signal is very low or too high
0010 0010
Module cannot be calibrated. Load cell signal
is very low or too high.
0010 0011
Calibration Error
- Calibration test weight is too small
- Increase calibration weight value (Write test
weight value from PLC Output to MCS-08Px
Input 2
nd
Dword then restart the calibration)
- Check load cell connections
0010 0101
Scale unstable
- Wait until scale becomes stable
- Check ground wiring
D11…D10
Not in use