Mcs-08px output to plc input – Flintec MCS-08 User Manual
Page 29
MCS-08 Technical Manual, Rev. 1.04 December 2012
Page 29 of 52
5.11. Profibus and ProfiNet Data Structure (for MCS-08Px only)
MCS-08Px Output to PLC Input
MCS-
08Px
1
st
Dword
(R)
D31 D30 D29 D28 D27 D27 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
Active MCS-08IO modules
Active MCS-08AD modules
D15 D14 D13 D12 D11 D10 D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
Error Table
Not in use
Read Data
Selected Resp.
CMD
flag
Bit no.
1
st
Dword Description
D31
0: No module found 1: MCS-08IO at address [7] is active
Active MCS-08IO
modules
D30
0: No module found 1: MCS-08IO at address [6] is active
D29
0: No module found 1: MCS-08IO at address [5] is active
D28
0: No module found 1: MCS-08IO at address [4] is active
D27
0: No module found 1: MCS-08IO at address [3] is active
D26
0: No module found 1: MCS-08IO at address [2] is active
D25
0: No module found 1: MCS-08IO at address [1] is active
D24
0: No module found 1: MCS-08IO at address [0] is active
D23
0: No module found 1: MCS-08AD at address [7] is active
Active MCS-08AD
modules
D22
0: No module found 1: MCS-08AD at address [6] is active
D21
0: No module found 1: MCS-08AD at address [5] is active
D20
0: No module found 1: MCS-08AD at address [4] is active
D19
0: No module found 1: MCS-08AD at address [3] is active
D18
0: No module found 1: MCS-08AD at address [2] is active
D17
0: No module found 1: MCS-08AD at address [1] is active
D16
0: No module found 1: MCS-08AD at address [0] is active
D15
D14
D13
D12
Error
Codes
0000
No error found
Error Codes of
MCS-08Px
0001
System failure. Re-energize module. If happens
again, replace module.
0010
EEPROM failure. Re-energize module. If happens
again, replace module.
0011
Gateway module error. Re-energize module.
Check if gateway module is installed. If happens
again, replace module.
0100
No module found on N-bus. Install MCS-08AD or
MCS-08IO modules. Check N-bus connectors if
installed.
0101
A module was installed/removed. Re-address the
modules on the N-bus.
D11…D4
Not in use
D3
D2
D1
Read
Command
Response
010
All active MCS-08AD modules refer to
D16…D31
Read selected
response
001
Active MCS-
08IO modules refer to D16…D31
000
All active modules refer to D16…D31 (default)
D0
Toggles
The command is applied successfully
CMD flag
MCS-
08 AD
[0]*
2
nd
Dword
(R)
D31 D30 D29 D28 D27 D27 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
D15 D14 D13 D12 D11 D10 D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
Indicated weight value will be shown in this Dword
3
st
Dword
(R)
D31 D30 D29 D28 D27 D27 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
Not In Use
D15 D14 D13 D12 D11 D10 D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
Error Table Of
MCS-08AD Modul
Count
mo
de
Z
ero
range
Net
Mo
ti
on
Response of Read Selected
Data.
CMD
flag