background image

MCS-08 Technical Manual, Rev. 1.04 December 2012

Page 22 of 52

4. Now change the address number on the Gateway Module by pressing the gateway switch (

YELLOW

) until it

reached an address you want to use for an MCS08AD or MCS08IO module.

5. To assign the selected address number to an A/D Converter or Digital I/O module press the setup switch on

the selected module (

BLUE

).

Please note: The MCS08 allows up to 8 A/D and 8 I/O in one system. A/Ds and I/Os
use the same address range (0 to 7). In consequence the same address can be
assigned to one A/D Converter AND one Digital I/O Module.

6. After assigning all modules to a defined address, press and hold the gateways switch for 5 seconds. The

system will close the addressing mode and change to normal mode

Note:

Do not de-energise MCS-08 while the system is in the addressing mode. If a power failure has

happened, restart the system and repeat the whole addressing.


LED and Setup Switch Descriptions in the N-Bus Addressing Mode:

Gateway module

Description of LED

Description of Setup Switch

Pwr

Lnk

Err

Address number is [0]

Increase to address number [1]

Address number is [1]

Increase to address number [2]

Address number is [2]

Increase to address number [3]

Address number is [3]

Increase to address number [4]

Address number is [4]

Increase to address number [4]

Address number is [5]

Increase to address number [6]

Address number is [6]

Increase to address number [7]

Address number is [7]

Jump to address number [0]

Address number is higher than [7]



MCS-08AD or MCS-08IO

Description of LED

Description of Setup Switch

Err

Defined N-bus address number and
gateway‟s selected address number
are identical

Assigns the gateway‟s selected address
number to its N-bus address number.

Defined N-bus address number and
gateway‟s selected address number
are different

Increase to address number [2]

Off

On

Flash

Table 5.2

– N-bus addressing via setup switch

5.9. Back up Settings and Calibration Data

The parameter settings and the calibration coefficients can be saved to a backup file after reading these data
from the MCS-08 modules. This backup file can be re-written to MCS-08 modules after opening it by xFace.
The backup feature gives a service advantage to MCS-08 systems. We propose to burn these files to CD /
DVD and save this backup CD / DVD in the control cabinet additionally to a backup file on your PC.

Important note: The previous parameter settings and calibration coefficients in a MCS-08 module will get lost
after loading a backup to this module.