Page 25 of 52

Address R/W

Word Command

Definition

40010*

R/W

1

Calibration

0

None

188

Adjust Zero Calibration

220

Adjust Span Calibration (First load 40011 with span test
weight value)

40011*

R/W

2

Span Calibration Value

40013*

R

1

Calibration
Status

D0 .. D7
Calibration
Process
Status

1

Ready for calibration

3

Zero calibration in process

4

Span calibration in process

9

Error (Refer to D8 ... D15 )

D8 .. D15
Calibration
Errors

1

Calibration Timeout
- Restart calibration

2

ADC Error
- Re-energize the instrument
- If seen again, change the board.

3

Instrument can not be calibrated
- Check load cell cable
- Re-energize the instrument

34

Instrument can not be calibrating
- Load cell signal is very low or too high

35

Calibration Error
- Calibration test weight is too small
- Increase calibration weight value (40011)
- Check load cell connections

37

Scale unstable
- Wait until scale becomes stable
- Check grounding wiring

40014*

R/W

1

Operation Mode
Selector

0

Count Mode Unipolar

1

Count Mode Bipolar

2

Force Mode Unipolar

3

Force Mode Bipolar

4

Weight Mode Unipolar

40015*

R/W

1

mV operation
in Count Mode

0

5 mV

1

10 mV

2

15 mV

3

18 mV

40016*

R/W

1

Digital filters

0

Fast

1

2

3

4

5

Medium

6

7

Default

8

9

Slow

N-bus address

0

1

2

3

4

5

6

7

*Starting register address

40001

40101

40201

40301

40401

40501

40601

40701


Address R/W

Word Command

Description

41001

R

1

System Status of
MCS-08AD and
MCS-08DP

D0

00: No module found at address [0]

D1

01: Module at address [0] is active

D2

00: No module found at address [1]

D3

01: Module at address [1] is active

D4

00: No module found at address [2]

D5

01: Module at address [2] is active

D6

00: No module found at address [3]

D7

01: Module at address [3] is active

D8

00: No module found at address [4]

D9

01: Module at address [4] is active