Alarms table – EVCO EPH4DXP1SA User Manual
Page 49
![background image](/manuals/675335/49/background.png)
EVCO S.p.A.
c-pro 3
hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204
page 49 of 52
7.
Alarms Table
Below find a list of the alarms managed by the application. The order of presentation is the same as the order with
which the alarms are presented when active. The alarms can also be all displayed with the machine off.
Code
Description of the alarm
Rearm
Consequence
Delay
AL01
External
temperature
probe
faulty
or
disconnected
Auto
Prevents
the
regulations
depending on the same
Can be set
AL02
Flow/return
temperature
probe
faulty
or
disconnected
Auto
Stops the unit
Can be set
AL03
Zone
2
temperature
probe
faulty
or
disconnected
Auto
Prevents
the
regulations
depending on the same
Can be set
AL04
Zone
1
temperature
probe
faulty
or
disconnected
Auto
Prevents
the
regulations
depending on the same
Can be set
AL05
Zone 1 humidity sensor faulty or disconnected
Auto
Prevents
the
regulations
depending on the same
Can be set
AL06
Dehumidifier block alarm
A/M
Dehumidifier collector and
booster stop
Can be set
AL07
Day zone anti-freeze alarm
A/M
Pump activation *
1
Can be set
AL08
Zone 2 anti-freeze alarm
A/M
Pump activation *
1
Can be set
AL09
HP block alarm
A/M
Chiller-hp control block
Can be set
AL10
Chiller block alarm
A/M
Chiller-hp control block
Can be set
AL11
Chiller-hp operating hours alarm
Manu*
2
Display
-
AL12
Pump operating time alarm
Manu*
2
Display
-
AL13
Flow switch alarm
Auto*
3
Switch-off all devices
Can be set
AL14
Configuration alarm
Auto
Stops the unit
-
AL15
High temperature lock alarm
A/M
Lock all loads
Can be set
AL15
High temperature lock alarm
A/M
Lock all loads
Can be set
A/M: Automatic or Manual alarm (can be set from parameter)
(*
1
) If the zone collector activates in anti-freeze period
(*
2
) To rearm the alarms linked to the operating hours, just zero the device hours.
(*
3
) Manual alarm after a number of alarms in one hour (PA03)