Label
Parameter description
Default
Min
Max
PA24
Zone 2 anti-freeze alarm rear type
0: Auto - Automatic
1: Manu - Manual
0 (auto)
0 (auto)
1 (manu)
PA25
Zone 2 anti-freeze alarm delay (seconds)
5
0
999
PA26
HP block alarm rearm type
0: Auto - Automatic
1: Manu - Manual
0 (auto)
0 (auto)
1 (manu)
PA27
HP block alarm delay (seconds)
5
0
999
PA28
Chiller lock alarm rearm type
0: Auto - Automatic
1: Manu - Manual
0 (auto)
0 (auto)
1 (manu)
PA29
Chiller block alarm delay (seconds)
5
0
999
PA30
Zone 1 anti-freeze set-point
3.0
-10.0
30.0
PA31
Zone 1 anti-freeze differential
1.0
0.0
10.0
PA32
Zone 2 anti-freeze set-point
3.0
-10.0
30.0
PA33
Zone 2 anti-freeze differential
1.0
0.0
10.0
INSTALLER PARAMETERS - VARIOUS
PH05
Enable machine switch-on/off by pressing the ESC/Stand-by
key
Yes (1)
No (0)
Yes (1)
PH07
Enable machine switch-on/off from supervisor
Yes (1)
No (0)
Yes (1)
PH08
Enable summer/winter operating mode from supervisor
Yes (1)
No (0)
Yes (1)
PH09
Enable summer/winter operating mode from digital input
No (0)
No (0)
Yes (1)
PH10
Enable summer/winter operation automatic switch-over on
Ext. T.
No (0)
No (0)
Yes (1)
PH11
Board Modbus address
1
1
247
PH12
Communication Baud Rate for the board (0=1200, 1=2400,
2=4800, 3=9600, 4=19200)
3
0
4
PH13
ModBus parity (0=none, 1=Odd, 2=Even)
2
0
2
PH14
Stop Bit ModBus (0=1bit, 1=2bit)
0
0
1
PH18
Delete alarms log
NO (0)
NO (0)
YES (1)
PH20
Board CAN address Baudrate (1=25K, 2=50K, 3=125K,
4=500K)
3
1
4
PH21
Can board address
1
1
8
PH32
Temperature unit of measurement:
0: °Celsius
1: °Fahrenheit
0 (°C)
0 (°C)
1 (°F)
PH33
Language
0: English
1: Italian
1
0
1
PH40
Day of the week for anti-grip (0=Sunday, ... ,
6=Saturday)
5
0
6
PH41
Time of anti-grip cycle start
2
0
23