EVCO EPH4DXP1SA User Manual
Page 46
EVCO S.p.A.
c-pro 3
hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204
page 46 of 52
Label
Parameter description
Default
Min
Max
MANUFACTURER PARAMETERS – DI CONF.
HDIL1
Digital input 1 logic
NC (1)
NO (0)
NC (1)
HDI1
Digital input 1 configuration
0: Disabled
1: Flow switch
2: Heat pump alarm
3: Chiller alarm
4: Summer/Winter
5: Dehumidifier alarm
6: Auxiliary hygrostat
7: Auxiliary thermostat
1
0
7
HDIL2
Digital input 2 logic
NO (0)
NO (0)
NC (1)
HDI2
Digital input 2 configuration
2
0
7
HDIL3
Digital input 3 logic
NO (0)
NO (0)
NC (1)
HDI3
Digital input 3 configuration
3
0
7
HDIL4
Digital input 4 logic
NO (0)
NO (0)
NC (1)
HDI4
Digital input 4 configuration
4
0
7
HDIL5
Digital input 5 logic
NO (0)
NO (0)
NC (1)
HDI5
Digital input 5 configuration
5
0
7
MANUFACTURER PARAMETERS – CONF. AO
HAO2
Analogue output 2 configuration
0: Disabled
1: Valve
2: Booster
3: Energy
1
0
3
HAO3
Analogue output 2 configuration
0: Disabled
1: Valve
2: Booster
3: Energy
2
0
3
HAOLB
Logic of the analog output hot/cold booster
NO (0)
NO (0)
NC (1)
HAOLC
Logic of the analog output energy recording
NO (0)
NO (0)
NC (1)
MANUFACTURER PARAMETERS – DO CONF.
HDOL1
Digital output 1 logic
NO (0)
NO (0)
NC (1)