EVCO EPH4DXP1SA User Manual
Page 13
![background image](/manuals/675335/13/background.png)
EVCO S.p.A.
c-pro 3
hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204
page 13 of 52
DIGITAL INPUTS
Digital inputs (potential-free contacts).
Clamp
Meaning
COM
common digital inputs
DI1
digital input 1
DI2
digital input 2
DI3
digital input 3
DI4
digital input 4
DI5
digital input 5
The maximum length of the digital input connection cables is 100 m (328 ft).
ANALOGUE INPUTS
Analogue inputs. (NTC)
Clamp
Meaning
AI1
analogue input 1
AI2
analogue input 2
AI3
analogue input 3
GND
earth
+5V
0-5 V ratiometric transducers power supply (5 VDC, 40 mA max.)
+24V
transducers power supply 0-20 mA / 4-20 mA / 0-10 V (24 VDC, 120 mA max.)
The maximum length of the analogue input connection cables and that of the transducers power supply is 100 m (328 ft).
The controller incorporates a restorable circuit breaker protection for the power supplies against short circuit and overload.
For the settings relative to the analogue inputs, see chapter 6 “CONFIGURATION”.
PROG
Port for programming and debug.