hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204
page 42 of 52
Label
Parameter description
Default
Min
Max
INSTALLER PARAMETERS - LINE
PL01
System line type
0: low temperature
1: high temperature
1
0
1
PL02
Low temperature line set-point (summer)
18.0
7.0
30.0
PL03
Low temperature line set-point (winter)
30.0
20.0
90.0
PL04
High temperature line set-point (summer)
12.0
5.0
30.0
PL05
High temperature line set-point (winter)
60.0
25.0
90.0
PL06
Dew point offset
3.0
0.0
10.0
PL10
High temperature set-point
45.0
0.0
90.0
PL11
High temperature differential
5.0
0.0
10.0
PL12
Low temperature set-point
10.0
-10.0
40.0
PL13
Low temperature differential
5.0
0.0
10.0
PL14
Lock high temperature alarm delay (minutes)
2
0
30
PL15
Type of lock high temperature alarm
0 – No
1 – Automatic
2 - Manual
1
0
2
PL16
Lock low temperature alarm delay (minutes)
2
0
30
PL17
Type of lock low temperature alarm
0 – No
1 – Automatic
2 - Manual
1
0
2
PL20
Chiller-hp activation delay from system line pump O
(seconds)
60
0
255
PL21
Regulation for heating/cooling external control
0: Valve lateral band
1: Valve maximum opening
2: Valve minimum opening
2
0
2
PL22
Chiller-hp switch-off delay with active zones request
(minutes)
1
0
30
PL23
Temperature delta for pump switch-off with chiller-hp in alarm
mode
5.0
0
10.0
PL24
Chiller-hp switch-off delay without active zones request
(seconds)
10
0
255
INSTALLER PARAMETERS - PUMP
PP01
Enable pump anti-grip cycle
1 (Yes)
0 (No)
1 (Yes)
PP02
System line pump On delay (seconds)
30
0
255
PP03
System line pump Off delay (seconds)
60
0
255
INSTALLER PARAMETERS - VALVE
PV01
Enable valve anti-grip cycle
1 (Yes)
0 (No)
1 (Yes)
PV02
Valve delay from System line pump ON
30
0
255
PV05
Valve min value
0.0
0.0
100.0
PV06
Valve max value
100.0
0.0
100.0
PV11
Minimum external temperature in Summer mode for
calculation of the shifting set-point
10.0
0.0
30.0