Configuration parameters
Below find the list of all configuration parameters managed by the MCSA application.
A brief description, the range of acceptable values, the unit of measurement and the proposed default value are
supplied for every description.
6.1.1
List of configuration parameters
Label
Parameter description
Default
Min
Max
USER PARAMETERS
OnOff
Machine status
0FF
0FF
ON
Mode
Summer/winter status from keyboard
E
E
I
SetEcoW Z.1
Zone 1 Economy Set-point (I)
16.0
10.0
30.0
SetComW Z.1
Zone 1 Comfort Set-point (I)
19.0
10.0
30.0
SetEcoS Z.1
Zone 1 Economy Set-point (E)
26.0
10.0
30.0
SetComS Z.1
Zone 1 Comfort Set-point (E)
23.0
10.0
30.0
SetMan Z.1
Zone 1 manual Set-point
26.0
10.0
30.0
SetH Z.1
Zone 1 Humidity Set-point
50.0
0.0
100.0
SetEcoW Z.2
Zone 2 Economy Set-point (I)
16.0
10.0
30.0
SetComW Z.2
Zone 2 Comfort Set-point (I)
19.0
10.0
30.0
SetEcoS Z.2
Zone 2 Economy Set-point (E)
26.0
10.0
30.0
SetComS Z.2
Zone 2 Comfort Set-point (E)
23.0
10.0
30.0
SetMan Z2
Zone 2 manual set-point
26.0
10.0
30.0
MAINTENANCE TECHNICIAN PARAMETERS - OPERATION
PM00
Pump maximum operating hours limit. The relative alarm will
be triggered over this limit
20000
0
100000
PM01
Pump operating hours
0
0
100000
PM02
Chiller-HP maximum operating hours limit. The relative alarm
will be triggered over this limit
20000
0
100000
PM03
Chiller -HP operating hours
0
0
100000
PM90
Last date that maintenance was performed on the machine
MAINTENANCE TECHNICIAN PARAMETERS - MANUAL
PM10
Manual/automatic operation of the DO1 output
0: Auto – automatic operation
1: Manu – manual operation
0 (Auto)
0 (Auto)
1 (Manu)
PM11
Manual/automatic operation of the DO2 output
0: Auto – automatic operation
1: Manu – manual operation
0 (Auto)
0 (Auto)
1 (Manu)
PM12
Manual/automatic operation of the DOE output
0: Auto – automatic operation
1: Manu – manual operation
0 (Auto)
0 (Auto)
1 (Manu)
PM13
Manual/automatic operation of the DO4 output
0: Auto – automatic operation
1: Manu – manual operation
0 (Auto)
0 (Auto)
1 (Manu)
PM14
Manual/automatic operation of the DO5 output
0: Auto – automatic operation
1: Manu – manual operation
0 (Auto)
0 (Auto)
1 (Manu)