EVCO EPH4DXP1SA User Manual
Page 41

EVCO S.p.A.
c-pro 3
hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204
page 41 of 52
Label
Parameter description
Default
Min
Max
PZ22
Zone 1 climatic curve max. ext T. (summer)
35.0
0.0
70.0
PZ23
Zone 2 climatic curve min. ext T. (summer)
12.0
0.0
70.0
PZ24
Zone 2 climatic curve max. ext T. (summer)
35.0
0.0
70.0
PZ25
Zone 1 climatic curve min. ext T. (winter)
-5.0
-30.0
40.0
PZ26
Zone 1 climatic curve max. ext T. (winter)
12.0
-30.0
40.0
PZ27
Zone 2 climatic curve min. ext T. (winter)
-5.0
-30.0
40.0
PZ28
Zone 2 climatic curve max. ext T. (winter)
12.0
-30.0
40.0
PZ29
Zone 1 climatic curve set-point delta
0.0
-10.0
10.0
PZ30
Zone 2 climatic curve set-point delta
0.0
-10.0
10.0
INSTALLER PARAMETERS - COLLECTORS
PC01
Zone 1 T set differential
1.0
0.0
10.0
PC02
Zone 2 T set differential
1.0
0.0
10.0
PC03
Zone 1 H set differential
5.0
0.0
20.0
PC04
Collectors off Delay (seconds)
30
0
900
PC11
Winter automatic switch-over threshold
5.0
-30.0
40.0
PC12
Summer automatic switch-over threshold
30.0
-30.0
40.0
PC13
Summer/Winter automatic switch-over delay (minutes)
1
0
255
INSTALLER PARAMETERS - DEHUMIDIFIER
PD01
Enable use of supplywater for dehumidification:
0 = Disabled
1 = Enabling complete chain
2 = Enabling heating/cooling only
1
0
2
PD02
Booster/dehumidifier restriction
1 (Yes)
0 (No)
1 (Yes)
PD03
Booster mode
0: None
1: Cooling
2: Heating
3: Cooling/Heating
3
0
3
PD04
Heating booster assignment
0: None
1: zone 1
2: zone 2
3: zone 1/zone 2
3
0
3
PD05
Cooling booster assignment
0: None
1: zone 1
2: zone 2
3: zone 1/zone 2
3
0
3
PD10
Zone 1 integration delta (winter)
1.0
0.0
10.0
PD11
Zone 1 integration delay (winter)
5
1
255
PD12
Zone 1 integration delta (summer)
1.0
0.0
10.0
PD13
Zone 1 integration delay (summer)
5
1
255
PD14
Zone 2 integration delta (winter)
1.0
0.0
10.0
PD15
Zone 2 integration delay (winter)
5
1
255
PD16
Zone 2 integration delta (summer)
1.0
0.0
10.0
PD17
Zone 2 integration delay (summer)
5
1
255