4 flow work set-point, 5 dew point control, Point – EVCO EPH4DXP1SA User Manual
Page 33: Dew point control
EVCO S.p.A.
5.2.4
Flow work set-point
The regulation set-point can be fixed or linked to a linear calculation on the temperature measurement of the external
air.
If the external air temperature probe is enabled and operating, then the regulation set
a climatic curve.
If the external air temperature probe is not present or broken, then the regulation set
via a relevant maintenance level parameter.
The set-point calculation climatic curve envisions setting two
These two pairs determine a minimum and maximum value of the set
per figure.
The two climatic curves and set-points differ for Summer or Winter mode, sep
seasons.
5.2.5
Dew point control
During SUMMER operating mode, the mixing valve work set
modified for the dew point control.
The dew point is the temperature at which a mass of air must be cooled at constant pressure, until it is saturated (i.e.
when the percentage of water vapour reaches 100%) and therefore can start to condensate if it should lose further
heat.
This would lead to the formation of dew on the cooled surface, thus compromising the integrity of the controlled
environment.
The dew point is calculated on the basis of the temp
To consider the construction features of the syst
be set by parameter.
The mixing valve regulation set-point (or of the flow line) will be limited to the minimum value given by the "flow dew
point + offset" calculated, whenever necessary.
If enabled, the lock alarm parameter for high and/or low temperature, after a delay set by parameter, will be disabled
all the loads.
c-pro 3
hecto MCSA | User manual ver.
page 33 of 52
point
point can be fixed or linked to a linear calculation on the temperature measurement of the external
If the external air temperature probe is enabled and operating, then the regulation set-point is calculated acco
If the external air temperature probe is not present or broken, then the regulation set-point is fixed; it is established
via a relevant maintenance level parameter.
point calculation climatic curve envisions setting two pairs of External Temperature -
minimum and maximum value of the set-point depending on the external temperature, as
points differ for Summer or Winter mode, separating the valve operation in the two
Dew point control
During SUMMER operating mode, the mixing valve work set-point will be monitored continuously and, if necessary,
temperature at which a mass of air must be cooled at constant pressure, until it is saturated (i.e.
when the percentage of water vapour reaches 100%) and therefore can start to condensate if it should lose further
dew on the cooled surface, thus compromising the integrity of the controlled
The dew point is calculated on the basis of the temperature and humidity of the zone 1.
To consider the construction features of the system, the dew point will be calibrated by a pre
point (or of the flow line) will be limited to the minimum value given by the "flow dew
point + offset" calculated, whenever necessary.
arm parameter for high and/or low temperature, after a delay set by parameter, will be disabled
| User manual ver. 2.0 | Code 144MCSAE204
point can be fixed or linked to a linear calculation on the temperature measurement of the external
point is calculated according to
point is fixed; it is established
- Set-point values.
point depending on the external temperature, as
arating the valve operation in the two
point will be monitored continuously and, if necessary,
temperature at which a mass of air must be cooled at constant pressure, until it is saturated (i.e.
when the percentage of water vapour reaches 100%) and therefore can start to condensate if it should lose further
dew on the cooled surface, thus compromising the integrity of the controlled
by a pre-defined offset that can
point (or of the flow line) will be limited to the minimum value given by the "flow dew
arm parameter for high and/or low temperature, after a delay set by parameter, will be disabled