EVCO EPH4DXP1SA User Manual
Page 12
![background image](/manuals/675335/12/background.png)
EVCO S.p.A.
c-pro 3
hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204
page 12 of 52
CO3/4/5
common digital output 3/4/5
NO3
digital output 3 normally open contact
CO4/5
common digital outputs 1 and 2
NO4
digital output 4 normally open contact
NO5
digital output 5 normally open contact
Digital output 6 (electro-mechanical relay)
Clamp
Meaning
CO6
common digital output 6
NO6
digital output 6 normally open contact
NC6
digital output 6 normally closed contact
The maximum length of the digital output connection cables is 100 m (328 ft).
The maximum current allowed on the loads is 3 A.
ANALOGUE INPUTS/OUTPUTS
Analogue outputs.
Clamp
Meaning
AI4
analogue input 4
AO1
analogue output 1 (PWM signal)
GND
earth
AO2
analogue output 2 (can be configured via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V
signal type)
AO3
analogue output 3 (can be configured via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V
signal type)
The maximum length of the PWM analogue output connection cables is 1 m (3.280 ft); that of the 0-20 mA / 4-20 mA / 0-10 V
analogue output connection cables instead is 30 m (98 ft).