1 electric connections (default configuration) – EVCO EPH4DXP1SA User Manual
Page 15
![background image](/manuals/675335/15/background.png)
EVCO S.p.A.
c-pro 3
hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204
page 15 of 52
2.3.1
Electric connections (default configuration)
Hereinafter the default I/O configuration for the three pre-set kind of machine. They can be modified by operating on
the dedicated parameter (PGUT) or on the dedicated parameters (manufacturer menu); see the dedicated paragraph.
PGUT = 1
-
zone 1 (temperature and humidity)
-
zone 2 (temperature)
-
Vroom.
I/O
Description
Zone controller
Analogue inputs
AI 1
External Temperature (NTC)
AI 2
Supply Temperature ( NTC)
AI 3
Zone 2 temperature (NTC)
Serial ports
RS 485
Modbus RTU protocol
CANbus
To the V-room (N.B. with V-room receive temp. probe °C and RH% signals via bus)
V-room temperature probe (zone 1)
V-room humidity probe (unique)
Digital inputs (potential-free contact ON-OFF)
DI 1
Mixing circuit flow switch
DI 2
Hot block alarm boiler
DI 3
Alarm – cooling block Chiller
DI 4
Remote summer winter
DI 5
Dehumidifiers alarm
Analogue outputs (PWM/0-10V/4-20mA)
AO 1
not available
AO 2
0-10 V flow modulating valve (or 4-20 mA to be ordered)
AO 3
Heating booster control (winter) or for cooling (summer)
Digital Outputs (Relay)
DO 1
collector_zone 1
DO 2
collector_zone 2
DO 3
Dehumidifier collector/dehumidifier consent
DO 4
Hot consent (Boiler or HP)
DO 5
Cold consent (Chiller)
DO 6
Apartment flow line circulation pump control