beautypg.com

EVCO EVFTFT618N7U User Manual

Page 45

background image

EVCO S.p.A.

EVFTFT618 | Installer manual ver. 2.2 | Code 144FTFT618E224

Page

45

of

62

1 = normally closed (input active with open contact)

i11

-1

240

s

5

input circuit breaker protection alarm signal delay

(“CtH”code)

-1 = the alarm will not be signalled

Par.

Min.

Max.

Unit

Default

Digital outputs

u1

0

1

- - - -

0

utility managed by the output K8

0 = pump down valve (in this case, parameter u2 will

have meaning)

1 = evaporator fan (in this case, the output will respond

to the status of the PWM output dedicated to the

evaporator fan in ON/OFF mode)

u2

0

240

s

90

if i6 = 0 or 1:

compressor deactivation delay from pump-down valve

switch-off (pump-down in switch-off only for u1 = 0)

If i6 = 2:

Pump-down maximum duration in compressor switch-off

mode without activation if the low pressure input such to

cause the compressor to switch-off and signal the pump-

down alarm.

0 = the alarm is not signalled

u3

0

1

- - - -

0

utility managed by the output K4

0 = dehumidifier/extractor fan (in this case, parameters

rU5 and rU6 will have meaning)

1 = condenser fan (in this case, the F16 and F17

parameters will assume significance)

N.B. with u3 = 1 dehumidification will be automatically

managed via the activation of the cooling plant

Par.

Min.

Max.

Unit

Default

Serial

communication

(RS-48

serial

port

with

MODBUS communication protocol)

L1

1

240

min

5

internal data sampling time

LA

1

247

- - - -

247

device address

Lb

0

3

- - - -

2

baud rate

0 = 2,400 baud

1 = 4,800 baud

2 = 9,600 baud

3 = 19,200 baud

LP

0

2

- - - -

2

parity

0 = none (no parity)

1 = odd

2 = even

Par.

Min.

Max.

Unit

Default

Other

E8

0

2

- - - -

2

keyboard lock

0 = disabled

1= manual