EVCO EVFTFT618N7U User Manual

Page 36

background image

EVCO S.p.A.

EVFTFT618 | Installer manual ver. 2.2 | Code 144FTFT618E224

Page

36

of

62

PF

Power supply cut-off during execution of a cycle alarm

Solutions:

-

check the device-power supply connection

COH

Condenser overheated alarm.

Solutions:

-

check the temperature of the condenser

-

check the value of the parameter C6.

Main consequences:

-

the condenser fan will be switched on

CSd

Compressor blocked alarm.

Solutions:

-

check the temperature of the condenser

-

check the value of parameters C7 and C8

-

disconnect the device power supply and clean the condenser.

Main consequences:

-

if the error occurs during an operating cycle, the cycle will be interrupted

PD

Pump-down alarm

Solutions:

-

check the maximum pump-down time established with parameter u2

-

the alarm will be rearmed on the successive activation of the compressor or by pressing the

buzzer silencing key

Main consequences:

-

compressor switch-off

Pr1

Cabinet probe error.

Solutions:

-

check the value of the parameter P0

-

check the integrity of the probe

-

check the device-probe connection

-

check the temperature of the cabinet.

Main consequences:

-

if the error occurs during the “stand-by” status, no operating cycles can be started

-

if the error occurs during a cycle, the cycle will be interrupted

Pr2

Evaporator probe error.

Solutions:

-

the same as the cabinet probe error (“Pr1” code) but relative to the evaporator probe.

Main consequences:

-

if parameter P3 is set at 1, the defrosting period will last for the amount of time set with

parameter 3

Pr3

Condenser probe error.

Solutions:

-

the same as the cabinet probe error (“Pr1” code) but relative to the condenser probe.

Main consequences:

-

the condenser fan will operate parallel to the compressor

-

the overheated condenser alarm (“COH” code) will never be activated

-

the compressor blocked alarm (“CSd” code) will never be activated