EVFTFT618 | Installer manual ver. 2.2 | Code 144FTFT618E224

Page

44

of

62

F23

0

100

%

35

evaporator fan min speed calibration value

F24

0

100

%

65

evaporator fan max speed calibration value

Par.

Min.

Max.

Unit

Default

Digital inputs

i0

0

2

- - - -

2

effect caused by opening the door, i.e. by activation of the

door micro switch

0 = no effect

1 = the compressor, the evaporator fan and the heater

will be switched off and the cabinet will be switched

on

2 = the evaporator fan and the heater will be switched

off and the cabinet light will be switched on

i1

0

1

- - - -

1

type of door micro switch input contact

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i2

-1

120

min

5

door open alarm signalling delay (“id” code)

-1 = the alarm will not be signalled

i3

0

1

- - - -

1

effect caused by the activation of the high pressure input

0 = no effect

1 = the compressor and the evaporator fan will be

switched off and the condenser fan will be switched

on

i4

0

1

- - - -

0

type of high pressure input 1

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i5

-1

240

s

5

high pressure alarm signalling delay (“HP” code)

-1 = the alarm will not be signalled

i6

0

2

- - - -

2

effect caused by the activation of the low pressure input

0 = no effect

t1 = alarm the compressor and the evaporator fan will be

off

2 = pump-down management and alarm. In the

compressor switch-off phase, the intervention of the

digital input will switch the compressor output off to

end the pump-down phase . During the cooling plant

activation phases, the intervention of the digital

input will switch the compressor and the evaporator

fan off

i7

0

1

- - - -

0

type of low pressure input 1

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i8

-1

240

s

10

low pressure alarm signalling delay (“LP” code)

-1 = the alarm will not be signalled

i9

0

240

s

40

low pressure switch rearm time on compressor switch on

(only if i6 =2)

i10

0

1

- - - -

1

type of circuit breaker protection input contact

0 = normally open (input active with closed contact)